...3 BASIC CONFIGURATION LEVEL

...3.4 Set Up Alarms

SEt UP
ALArMS
ACKtYP
LAtCH
NOrMAL
NONE
ACKSrC
ALM d4
NONE
SELECt
ALM d4
Ch. 4
ALM A4
ALM d3
Ch. 3
ALM A3
ALM d2
Ch. 2
ALM A2
ALM d1
Ch. 1
ALM A1
NONE
NONE
12
Page Header – Set Up Alarms
To advance to
Set Up Relay Output
Alarm Acknowledge Type
Alarms may be acknowledged while they are displayed.
Select the alarm acknowledge type:
NONE
no acknowledge facility. If the cause of the alarm no longer exists, the alarm
state and display are cleared automatically.
Alarm cause
Present
Not Present
NOrMAL
and
LAtCH
Alarm cause
Present
Present
Not Present
Present
Not Present
Not Present
*Alarm state is active if
Global Alarm Acknowledge Source
Select the alarm acknowledgment source required.
For a description of sources – see
Select Alarm
Select the alarm to be programmed.
Note. In the remaining frames press the
Continued on next page.
page press the
L.E.D.
Flashing
Off
if the cause of the alarm no longer exists, the alarm
display remains until it has been acknowledged.
Acknowledge
No
Yes
Previously acknowledged
No
No
Yes
LAtCH
is selected or inactive if
on page 15.
Table 3.1
switch to view the alarm selected.
switch.
Alarm State
Active
Inactive
L.E.D.
Alarm State
Flashing
Steady
Off
Inactive
Flashing
Flashing
Active/Inactive*
Off
Inactive
NOrMAL
is selected
Active
Active
Active