Siemens Simovert 6SE70 Series Operating Instructions Manual page 212

Master driver rectifier/regenerating unit sizes c to k
Table of Contents

Advertisement

https://www.aotewell.com
Fault and Alarm Messages
Fault
Fault description
No.
F103
Thy/Grnd Flt
Fault when conducting the
thyristor/ground-fault test
This fault message can only occur if the
thyristor/ground-fault test is activated with
parameters P353 / P354.
A software check is made to see whether
all thyristors have blocking capability,
whether they can be fired, and whether
there is a ground fault
Identification of the firing lines and the
associated thyristors should always be
made with the aid of the relevant wiring
diagram (see Section 3-5 "Power
terminals").
F116
Fault on the intelligent I/O module
to
See User's Manual of the TB module
F150
7-8
AoteWell LTD
AoteWell Automation Sales Team
Fault
Meaning
value
Short-circuit of thyristor V11 or V24
1
2
Short-circuit of thyristor V12 or V25
3
Short-circuit of thyristor V13 or V26
4
Short-circuit of thyristor V14 or V21
5
Short-circuit of thyristor V15 or V22
6
Short-circuit of thyristor V16 or V23
8
Ground fault in DC link or in motor /
rectifier fuse defective
9
I = 0 - Message defective
11
Thyristor cannot be fired (X11)
12
Thyristor cannot be fired (X12)
13
Thyristor cannot be fired (X13)
14
Thyristor cannot be fired (X14)
15
Thyristor cannot be fired (X15)
Thyristor cannot be fired (X16)
16
17
2 or more thyristors of the rectifier
bridge cannot be fired
21
Thyristor cannot be fired (X21)
22
Thyristor cannot be fired (X22)
23
Thyristor cannot be fired (X23)
24
Thyristor cannot be fired (X24)
25
Thyristor cannot be fired (X25)
26
Thyristor cannot be fired (X26)
27
2 or more thyristors of the
regenerative bridge cannot be fired
31
Thyristor cannot block
(gate X11 or X21)
32
Thyristor cannot block
(gate X12 or X22)
33
Thyristor cannot block
(gate X13 or X23)
34
Thyristor cannot block
(gate X14 or X24)
35
Thyristor cannot block
(gate X15 or X25)
36
Thyristor cannot block
(gate X16 or X26)
-
-
Buy Siemens PLC HMI Drives at AoteWell.com
Sales@aotewell.com
Possible causes
Countermeasures
- Thyristor defective
- Thyristor externally shorted
(e.g. by ground fault in grounded
system and ground fault in the
motor)
- Connection to DC link interrupted
(e.g. fuse blown)
Possible reasons for the thyristor
being defective:
- Interruption in the RC circuit
- Converter and compensation
control not optimized (excessive
current peaks)
- Cooling not guaranteed (e.g. fan
not running, ambient temperature
too high, to little air intake, heat
sink severely contaminated)
- Excessive voltage peaks in
supply system
- Ground fault
- Connection to DC link interrupted
(e.g. fuse blown)
- CUR module defect
- Firing pulse line to relevant
thyristor interrupted
- Ribbon cable X109 not correctly
plugged in or interrupted (and
ribbon cable X27 in the case of
power section connected in
parallel)
- Defect in electronics and/or
power interface module
- internal interruption on the gate
line in the thyristor module
- Connection to DC link interrupted
(e.g. fuse blown)
- As under 11 to 16
- As under 11 to 16
- Parameter P076 wrong
- As under 11 to 16
- As under 1 to 6
-
Siemens AG
6SE7087-6AK85-1AA0
Rectifier/Regenerating Unit
Operating Instructions