9.3

Units connected to the RS232 interface J7

9.3.1

Web-servers

1598
Web-server II. This unit can be used in the following applications:
a)
b)
c)
c1) EBL Talk (RS232 or TCP/IP) is an open protocol, used to transmit and
c2) Tateco (RS232) used to transmit and present fire alarm information in an
c3) SIA (RS232) used to transmit and present fire alarm information in a
c4) MODBUS (RS232)
d)
licence required.
The Web-Server has to be preconfigured with proper TCP/IP protocols using
@CHIPTOOL before setting up the Web-Server SSD configuration in the PC
program EBLWin. The Web-Server SSD configuration is downloaded to the Web-
Server via TCP/IP using an Ethernet cable. The Web-Server software is also
downloaded via the PC program EBLWin.
The Web-server II consists of a light grey plastic enclosure (90x25x69.5 mm),
which can be mounted on a 35 mm DIN rail inside the FT1020G3 CIE
Web-server II has the following interfaces:
RS232 (PLC COM) to connect the web-server to J7 in the FT1020G3 CIE
RS232 (MODEM COM) to connect the web-server to other PC / system
RJ45 (10 BASE-T) to connect the web-server to Internet / an intranet (LAN)
Molex 3.5 to connect the web-server to J3 (24 V
Details for setting up the Web-Server is found in MA440 Web Server II Manual Rev
1.0 for FT1020G3 and FT128.
9.4

Other units

9.4.1

External LEDs

BARIL Remote Indicator RIL. Used when a detector is placed out of view or hidden e.g.
roof space detectors. The LED is lit at the same time as the LED in the detector /
base that is connected to. It has a "Burning house" symbol instead of any text.
BARIL can be connected to all types of Panasonic detectors / bases. The input is
polarised.
J2:1 (+5 to +35 V
J2:2 (< 25 mA) for Analogue detectors / bases
J2:3 (0 V)
To be wall mounted (87 x 87 x 39 mm)
75
Consists of 6 digits.
For presentation of the actual CIE status on a PC using a web browser such
as Microsoft Internet Explorer. It can also send e-mails in case of pre-warning,
fire alarm, fault, disablement and test mode alarm and/or service signal.
For remote control via two-way communication. Up to 10 User names with an
75
individual Password
and three different access levels.
As a gateway to other PC systems etc.:
present fire alarm information in a separate PC / system.
Ascom Tateco paging system.
separate PC application.
information in a separate PC application.
As a gateway to a security management system via EBLnet. (TCP/IP) EBLnet
) for Conventional detectors / bases
DC
70
Technical/Programming Manual
used to transmit and present fire alarm
) in the FT1020G3 CIE
DC
FT1020G3 Rev 2.2.1