Programmable outputs

FT1020G3 has four programmable voltage outputs S
outputs R
-R
0
with three programmable outputs (Output 0-2) can be mounted in FT1020G3. See chapter
"Expansion boards 458x", page 24.
On the COM loops, Addressable Multipurpose I/O units 3361 with two programmable relay
outputs (Re
connected.
beacon 4380 and light indicator 4383 can also be connected on the COM loops, i.e. the
units have no physical outputs, only siren, sounder and light respectively.
Notes:
Each output is programmed via EBLWin, when applicable for the following
Name (Normally not changed)
Type
Signal period (continuous, pulse, delay, etc.)
Logic (NO / normally low or NC / normally high)
Supervised / Non-Supervised (The voltage outputs in FT1020G3 and in the
Addressable 2 voltage outputs unit 3364)
Control expression (with one or more trigger conditions)
If "Enter arguments in dialog" is selected, a separate dialog box is opened for easier
entering of the required data (e.g. zone, address, etc.). SSD size indicates how big the
control expression is. It must be < 80.
Each 3379, 4477, 3378 and 3379 unit is programmed via EBLWin for the following:
Technical address
Name (Normally not changed)
Priority level (High / Medium / Low)
. 8 relays expansion boards 4581 and Input / Output expansion board 4583
1
-Re
) per unit and Addressable 2 voltage outputs units 3364 can be
0
1
Addressable siren 4477, Addressable sounder base 3379, Addressable
Units type 3379 + 4477 (or old type 3377) = maximum 50 per loop.
Units type 4380 = maximum 10
Figure 28 EBLWin Voltage & Relay Output dialog boxes
Technical/Programming Manual
-S
and two programmable relay
0
3
79
FT1020G3 Rev 2.2.1