For Network Configuration; System Configuration; Parameter Setting - Mitsubishi Electric MELSEC iQ-R Series Reference Manual

Inter-module synchronization function
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

7.2

For Network Configuration

The following is an example of a program that outputs to the adjacent output module and multiple output modules via the
network at the inter-module synchronization cycle timing.

System configuration

The following system configuration is used.
Master station side
• CPU module: R120CPU
• Each module: RX10, RY40NT5P, RJ71GF11-T2
Local station side
• CPU module: R04CPU
• Each module: RY40NT5P, RY40NT5P, RJ71GF11-T2

Parameter setting

This section shows the details of each parameter setting.
Master station side
This section shows the details of the master station side parameter settings.
■Inter-module synchronization setting
This table shows the details of the inter-module synchronization settings.
Item
Use Inter-module Synchronization Function in System
Select Inter-module Synchronization Target Module
Fixed Scan Interval Setting
■Network configuration setting
Add the local station with the network configuration settings.
Set "Network Synchronous Communication" to "Synchronous".
■Refresh settings
Set the transmission range between the RJ71GF11-T2 and the CPU module devices.
[Module Parameter]  "Basic Settings"  "Refresh Settings"
Description
Select "Use".
Select "Synchronize" for all.
1.00ms (select "Set in 0.05ms unit")
7.2 For Network Configuration
7 PROGRAM EXAMPLES
7
41