ABB ACS 600 Startup Manual page 5

Frequency converters equipped with standard application program 5.x
Hide thumbs Also See for ACS 600:
Table of Contents

Advertisement

Enter the motor data from the motor nameplate.
3
motor
Hz
V
690 Y
50
400 D
50
660 Y
50
380 D
50
415 D
50
440 D
60
Cat. no
3GAA 202 001 - ADA
6312/C3
Note: Set the motor data exactly the same as on the motor
nameplate. For example, if the motor nominal speed is
1440 rpm on the nameplate, setting the value of Parameter
99.08 MOTOR NOM SPEED to 1500 rpm results in wrong
operation of the drive.
Nominal voltage. The general parameter setting procedure
is given on Page 2.
Allowed range: 1/2 · U
voltage in each of the nominal voltage ranges: 415 VAC for 400 VAC
units, 500 VAC for 500 VAC units and 690 VAC for 600 VAC units.)
Nominal current. The general parameter setting procedure
is given on Page 2.
Allowed range: 1/6 · I
Nominal frequency. The general parameter setting
procedure is given on Page 2.
Range: 8 ... 300 Hz
Nominal speed. The general parameter setting procedure
is given on Page 2.
Range: 1 ... 18000 rpm
Standard Application Program
START-UP PROCEDURE
ABB Motors
M2AA 200 MLA 4
IEC 200 M/L 55
No
Ins.cl. F
kW
r/min
A
cos
30
1475
32.5
0.83
1475
56
0.83
30
1470
34
0.83
30
30
1470
59
0.83
1475
30
54
0.83
35
1770
59
0.83
6210/C3
IEC 34-1
... 2 · U
of ACS 600. ( U
N
N
... 2 · I
of ACS 600
2hd
2hd
IP 55
IA/IN t E/s
380 V
Mains
Voltage
180
refers to the highest
N
Start-up Guide
1
->
0.0 rpm
99 START-UP DATA
05 MOTOR NOM VOLTAGE
[ ]
1
->
0.0 rpm
99 START-UP DATA
06 MOTOR NOM CURRENT
[ ]
1
->
0.0 rpm
99 START-UP DATA
07 MOTOR NOM FREQ
[ ]
1
->
0.0 rpm
99 START-UP DATA
08 MOTOR NOM SPEED
[ ]
O
O
O
O
3

Advertisement

Table of Contents
loading