ABB ACS 600 Startup Manual page 3

Frequency converters equipped with standard application program 5.x
Hide thumbs Also See for ACS 600:
Table of Contents

Advertisement

The start-up procedure must only be carried out by a qualified electrician.
The safety instructions must be followed during the start-up procedure. See the
appropriate hardware manual for the safety instructions.
The ACx 600 must not be powered up more than five times in ten minutes to avoid
charging resistor overheating (no limitation for ACS 600 MultiDrive and ACx 607
units -0760-3, -0930-5, -0900-6 or above).
Check the installation before the start-up procedure. See the installation checklist from the
appropriate hardware/installation manual.
Check that starting the motor does not cause any danger.
It is recommended having the driven equipment disengaged when first start is performed if
there is the risk of damage to the driven equipment in case of incorrect rotation direction of
the motor.
Apply mains power. The Control Panel first enters the
panel identification data ...
... then the Identification Display of the drive ...
...and after a few seconds the Control Panel automatically
enters the Actual Signal Display.
Drive set-up can be started.
Standard Application Program
START-UP PROCEDURE
1 – SAFETY
2 – POWER-UP
Start-up Guide
CDP312 PANEL
.......
ACS 600
xx kW
ID NUMBER 1
1
->
0.0 rpm
FREQ
0.00 Hz
CURRENT
0.00 A
POWER
0.00 %
Vx.xx
O
1

Advertisement

Table of Contents
loading

Table of Contents