through the communication cables, described below.
5V DC version GT1020 GOTs
The GT1020-LBL and GT1020-LBLW are the only two 5V DC GOTs in
the GOT1000 lineup. They are powered directly from the communication
cable, and can only be connected with an FX Series PLC. Other PLCs and
connectable products will not provide the necessary 5V DC power. The
power terminals have been removed from the 5V DC versions.
Communication
For the GT1020/GT1030 to communicate with an FX Series PLC, a
dedicated communication cable is required to connect the provided PLC
Communication Connector with the Programming Port (RS-422 8-pin Mini-
DIN) or other communication channel of the FX (RS-422 8-pin Mini-DIN or
RS-232C 9-pin D-sub). The cable names and length and specific wiring for
each case are illustrated below:
Connection to an RS-422 FX communication channel
Cable Name
GT10-C10R4-8P*
GT10-C30R4-8P*
GT10-C100R4-8P
GT10-C200R4-8P
GT10-C300R4-8P
* - Only the GT10-C10R4-8P and GT10-C30R4-8P apply to the GT1020-LBL and GT1020-
LBLW GOTs (5V DC versions).
Connection to an RS-232C FX communication channel
Cables
All RS-232C
GT1020/GT1030-to-FX
connection cables must be
made by the user as
described below.
Note: This document is for reference only. For detailed settings and safety information refer to the respective product manual.
Length
Applicable GOTs
1m
GT1020-LBD
3m
GT1020-LBDW
10m
GT1030-LBD
20m
GT1030-LBDW
30m
Applicable GOTs
GT1020-LBD2
GT1020-LBDW2
GT1030-LBD2
GT1030-LBDW2
FX Comm. Equipment
Programming Port
FX3U-422-BD
FX2N-422-BD
FX1N-422-BD
FX Comm. Equipment
FX3U-232-BD
FX3U-232ADP(-MB)*
FX2N-232-BD
FX2NC-232ADP*
FX1N-422-BD
3