Open Fuse Lockout Device Diagram - GE AK-2-50 Maintenance Manual

Low-voltage power circuit breakers
Table of Contents

Advertisement

GEK-7303
Low
Voltage Power Circuit Breakers
for the reset button (10). To adjust reset button,
loosen lock nut ahead of reset button
&
turn
button until :proper adjustment is made.
Re-
tighten lock nut.
REPLACEMENT
If
it becomes
necessary
to replace coil (6)
proceed as follows:
·
1.·
Remove five bolts connecting the device
to the
side plate and front frame. Lower
.
lockout device, guiding rod (3) thru rod
15
5------t
6 - - - - - - - - '
.
7 - - - - - - - - - - '
8---------.J
14
guide
(2).
Continue
lowering
the device
until movement is restricted
by
the device
wiring harness.
2.
Disconnect
leads
to coil (6).
3.
Remove two screws holding the trip device
to
the device mounting
plate.
4.-
Bend
lower
e.nd ~f brass ·clamp straight.
5.
Remove coil.
Install new
coil and replace
parts in reverse order.
I
TRIP
.
PADDLE·
2 ROD GUIDE
.
3
ROD
4 LOCK NUT
.
.
5
1'.RIP DEVICE
t
COIL
7
LINK ASSEMBLY
8
ARMATURE
9 ARM
..
10 RESET BUTTON
I
I ROD. RESET eu,:TON
12 SPRINGS. RESET ROD
·
13
SPRING.
LINK ASSEMBLY
14·
MOUNTING BRACKET
15 TRIP SHAFT
~ - - - - - - - - ~ 1 3
~--~------12
~--------11
~---10
F!g.
47
(0133C9024) Open
Fuse Lockout
Device

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents