Testing Magnetic Coils; Replacement Of Power Sensor Components - GE AK-2-50 Maintenance Manual

Low-voltage power circuit breakers
Table of Contents

Advertisement

Low
Voltage
Power
Circuit
Breakers GEK-7303
Fig.
33 (8039646)
Magnetic Coil Assembly
for
AK-3 75, 100 Breakers (Only)
·
(Mounted on
Assembly Fixture)
·
.
1
.
Power
Sensor Coil Assembly
2. Transformer Taps in Ampere
3
•.
Disconnect Plug
to
either
terminal·
at
·
remote
C.
T. and
check
to
assure the shield
is
continuous from Power
Sensor
Plug
..
to remote C.T. by checking for
continuity
between R and A.
If
continuity
does not
now
exist, shield is
not continuous
and the point of
discontinuity
must be
found~ Check
the
control
disconnect as the possible point of discontinuity.
Remove.
jumper
at remote C.T.
after_shield
c;:on:.
tinuity is
establi~~ed.
·
·
Note the
po_
l arity marks
on
the grounc!_sensors. ~e
sure
the external
ground
C.
T.
senses the neutral
current
associated
with the
particular
breaker
load current and that polarity marks are in
ac-
cordance
with Fig. 40.
If
the breakerbottom studs
connect to the
source,
the
external
C.T.
must
also
·
have its polarity ~,;irk toward the
source.
TESTI
N
~
_
MAGNETI
C COILS
After
the PST-1 Test Kit
has
been used to deter-
mine the adequacy of
perf~rmance
o! t1?e Power
.
Sensor Unit
and the .Power SUpply Unit, it may be
advisable or
required to test the
magnetic coils
by
the use
of
a Hi-current- Low voltage
type
test
set.
In this event·on1y one-test
per
phase
need be
made.
This test should be made
at·
s ome convenient multi-
ple of
pick-
up
·
setting
such
as 3 X
current setting
for
comparison with published
time-
current curves.
In the event the breaker is equipped with ground
sensor,
the ground sensor will
cause
tripping
on
single pole testing unless the signal
is short.ed
at the terminal board Fig.
(40).
Short point
4.
Terminal
Board
5.
External Ground Sensor
Lead
1
and
5
during overcurrent
test.
.
.
The above
considerations should
indicate which of
·
the·
four
major components is
faulty
and
in
need
of
replacement.
REPLACEMENT OF POWER
-
SENSO
R
COMPONENTS
.
Power Sensor
Unit
"(Fig~ 35)
1.
_
Loosen
screw·
connecting the uni~ tq
th_
e
front
frame.
·
2.
Slide unit
forward.
3
.
Remove
control plug
by alternately loosen-:
-
ing
th~
two retaining
screws.
4.
Replace in reverse order.
Trip
Solenoid (Fig. 36)
1.
Remove.
opening springs
2.
Raise cross bar to gain
additional access
room
3,
Remove two
nuts
holding device to bracket
4.
Remove
wiring cleats
and
connections
to
terminal board
on
Power Supply to free the
·
trip
solenoid for
removal

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents