Troubleshooting

PORT Status Indicator

Status
Cause
Off
The adapter is not powered
or is not connected
properly to the drive.
Flashing Red
The adapter is not
receiving a ping message
from the drive.
Solid Red
The drive has refused an
I/O connection from the
adapter.
Another DPI peripheral is
using the same DPI port as
the adapter
Orange
The adapter is connected
to a product that does not
support Allen-Bradley DPI
communications
Flashing Green
The adapter is establishing
an I/O connection to the
drive.
Solid Green
The adapter is properly
connected and is
communicating with the
drive.
Corrective Action
Securely connect the adapter to the drive
using the ribbon cable.
Apply power to the drive.
Verify that cables are securely connected.
Cycle power to the drive.
Important: Cycle power to the drive after making
any of the following corrections:
Verify that all DPI cables are securely
connected and not damaged. Replace
cables if necessary.
Verify that the DPI Host supports Datalinks.
Configure the adapter to use a Datalink that
is not already being used by another
peripheral.
Connect the adapter to a product that
supports Allen-Bradley DPI communications
(for example, PowerFlex drives).
No action. Normal behavior if no DPI I/O is
enabled.
No action.