Installation Instructions 1734 POINT I/O EtherNet/IP Adapter Catalog number 1734-AENT, Series B Table of Contents Topic Page Important User Information Environment and Enclosure Preventing Electrostatic Discharge Additional Resources North American Hazardous Location Approval European Hazardous Location Approval About The Adapter...
2 1734 POINT I/O EtherNet/IP Adapter Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some important differences between solid-state equipment and hard-wired electromechanical devices.
1734 POINT I/O EtherNet/IP Adapter Environment and Enclosure ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such environments.
1770-IN041. techniques. If you would like a manual, you can: • download a free electronic version from the internet: http://www.rockwellautomation.com/literature/ • purchase a printed manual by contacting your local Allen-Bradley distributor or Rockwell Automation representative. Publication 1734-IN042D-EN-P - October 2015...
1734 POINT I/O EtherNet/IP Adapter North American Hazardous Location Approval The following information applies when Informations sur l’utilisation de cet operating this equipment in hazardous équipement en environnements dangereux: locations: Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for Les produits marqués "CL I, DIV 2, GP A, B, C, D"...
6 1734 POINT I/O EtherNet/IP Adapter European Hazardous Location Approval The following applies when the product bears the Ex Marking This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC and has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in Zone 2 potentially explosive atmospheres, given in Annex II to this Directive.
1734 POINT I/O EtherNet/IP Adapter About The Adapter The Series B 1734-AENT POINT I/O EtherNet/IP Adapter is a communications adapter for POINT I/O modules. The adapter provides an interface for controlling and communicating with POINT I/O modules from an EtherNet/IP network.
Firmware Backward Compatibility The 1734-AENT Add-on Profiles are compatible with RSLogix 5000 software version 16, or greater. If you use the 1734-AENT adapter with a 1756-ENBT module, use the following required firmware versions for these bridge modules: • 1756-ENBT firmware version 4.006 or greater •...
Install the Adapter Follow this procedure to install the adapter on the DIN rail. ATTENTION: You must only use Series C POINT I/O modules with 1734-AENT EtherNet/IP Adapters. Series A or Series B POINT I/O modules will not work with 1734-AENT EtherNet/IP Adapters (does not apply to POINTGuard modules).
Page 10
10 1734 POINT I/O EtherNet/IP Adapter 2. Press down firmly to install the adapter on a DIN rail, noting that the locking mechanism locks the adapter to the DIN rail. 3. Set the network address thumbwheel switches to the desired value. See Set the Network Address for more information on setting the IP address.
1734 POINT I/O EtherNet/IP Adapter Set the Network Address The thumbwheel switches are set to 999 and DHCP enabled, by default. You can set the network Internet Protocol (IP) address in the following ways: • Use the thumbwheel switches on the adapter. •...
Page 12
12 1734 POINT I/O EtherNet/IP Adapter If you set the switches to an invalid number (for example, 000 or a value greater than 254 excluding 888), the adapter checks to see if you enabled DHCP. DHCP Enabled and Not Enabled DHCP State Adapter Action Enabled...
1734 POINT I/O EtherNet/IP Adapter Replace The Adapter Use these procedures to install a replacement adapter to an existing system. 1. Disconnect the Ethernet connector(s) from the adapter. 2. Pull up on the Removable Terminal Block (RTB) handle to remove the terminal block.
Page 14
14 1734 POINT I/O EtherNet/IP Adapter 9. Press firmly to seat the adapter on the DIN rail, noting that the adapter locking mechanism will snap into place. 10. Set the node address on the node address thumbwheel. 11. Insert the end of the terminal block opposite the handle into the base unit, noting that this end has a curved section that engages with the wiring base.
1734 POINT I/O EtherNet/IP Adapter Wire The Adapter Ethernet RJ-45 connector Chas Gnd 43264 NC = No Connection Chas GND = Chassis Ground C = Common V = Supply Chas Chas V DC IMPORTANT Do not connect 120/240V AC power to this supply. This DC supply will be connected to the internal power bus.
Page 16
16 1734 POINT I/O EtherNet/IP Adapter WARNING: Do not wire more than two conductors on any single terminal. WARNING: To comply with the CE Low Voltage Directive (LVD), this equipment must be powered from a Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV) compliant source.
1734 POINT I/O EtherNet/IP Adapter Interpret Status Indicators Refer to the following diagram and table for information on how to interpret the status indicators. POINT I/O EtherNet/IP Adapter, Series B Network address thumbwheels Module status Network activity Network status Ethernet RJ-45 connector POINTBus status System power Field power...
Page 18
18 1734 POINT I/O EtherNet/IP Adapter Indicator Status for Modules Network No link established. Activity Flashing green/Off Transmit or receive activity present. Steady green Link established. Network Device not initialized. The module does not have an IP address. status Flashing green No CIP connections present.
1734 POINT I/O EtherNet/IP Adapter Specifications POINT I/O EtherNet/IP Adapter — 1734-AENT, Series B Attribute Value Expansion I/O capacity, max • 63 modules • Up to 5 rack-optimization (for digital modules only) and/or enhanced rack-optimization (for digital, analog, and specialty modules) connections •...
20 1734 POINT I/O EtherNet/IP Adapter Power Supply Attribute Value Inrush current, max 6.0A for 10ms Input overvoltage protection Reverse polarity protected POINTBus output current, max 5V DC @ 1.0A Interruption Output voltage will stay within specifications when input drops out for 10ms at 10V with maximum load.
1734 POINT I/O EtherNet/IP Adapter General Specifications Attribute Value Field power output 10...28.8V DC @ 9A Module input 10...28V DC @ 1000 mA POINTBus output, max 5V DC @ 1.0A Dimensions (HxWxD), approx. 76.2 x 54.9 x 133.4 mm (3.0 x 2.16 x 5.25 in.) Enclosure type rating None (open-style) Terminal base screw torque...
Page 23
1734 POINT I/O EtherNet/IP Adapter Certifications Certification (when Value product is marked) c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. European Union 2004/108/EC EMC Directive, compliant with:...
RA-DU002, available at http://www.rockwellautomation.com/literature/. Allen-Bradley, Rockwell Automation, POINT I/O, and TechConnect are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies. Publication 1734-IN042D-EN-P - October 2015...