Section 3 Interface Modules; Eight Copper Ports; Interface Specifications - ABB NE870 User Manual

800xa networks
Table of Contents

Advertisement

Section 3 Interface Modules

Eight Copper Ports

All ports support category 5e cable or better and can handle cable lengths up to 150
m (492 ft).

Interface Specifications

8-Copper Ports
Electrical specification
Data rate
Duplex
Circuit type
Transmission range
Isolation to
Connection
Shielded cable
Conductive housing
Number of ports
* Note: Railway installation close to the rails. To minimise the risk of interference, a shielded cable is recommended when
the cable is located inside 3 m boundary to the rails and connected to this port. The cable shield should be properly
connected (360°) to an earthing point within 1 m from this port. This earthing point should have a low impedance
connection to the conductive enclosure of the apparatus cabinet, or similar, where the unit is built-in. This conductive
enclosure should be connected to the earthing system of an installation and may be directly connected to the
protective earth. For more information, see "Safety".
3BSE083159
Section 3 Interface Modules
IEEE std 802.3. 2005 Edition
10 Mbit/s or 100 Mbit/s, Manual or Auto
Full or half, Manual or Auto
TNV-1
Up to 150 m with CAT5e cable or better*
All other
RJ-45 auto MDI/MDI-X
Not required, except when installed in Railway
applications as signalling and telecommunications
apparatus and located close to rails*
Yes
8
21