ABB NE870 User Manual page 15

800xa networks
Table of Contents

Advertisement

Section 2 Interface specifications
USB
Electrical
specification
Data rate
Circuit type
Maximum supply
current
Isolation to
Connection
Conductive housing Yes
IO / Relay output
Connect
resistance
Isolation to
Connection
Connector size
Maximum
voltage/current
IO / Digital input
Voltage levels
Isolation to
Connection
Connector size
Maximum voltage
3BSE083159
USB 2.0 host
interface
High speed
480mbit/s
SELV
500 mA
All other except
Console
USB receptacle
connector type A
30 W
All other
Detachable
screw terminal
0.2–2.5 mm2
(AWG 24–12)
60 VDC/80 mA
Vih>8V Vil<5V
Iin=2.9mA @60V
All other
Detachable
screw terminal
0.2–2.5 mm2
(AWG 24–12)
60 VDC
Ethernet TX
Electrical
IEEE std 802.3. 2005 Edition
specification
Data rate
10 Mbit/s, 100 Mbit/s, 1000
Mbit/s, manual or auto
Duplex
Full or half, manual or auto
Circuit type
TNV-1
Transmission
Up to 150 m with CAT5e cable
range
or better*
Isolation to
All other
Connection
RJ-45 auto MDI/MDI-X
Shielded
Not required, except when
cable
installed in Railway applications
as signalling and telecommuni-
cations apparatus and located
close to rails*.
Conductive
Yes
housing
No. of ports
3
* Note: Railway installation close to the rails.
To minimise the risk of interference, a
shielded cable is recommended when the
cable is located inside 3 m boundary to the
rails and connected to this port. The cable
shield should be properly connected (360°) to
an earthing point within 1 m from this port.
This earthing point should have a low
impedance connection to the conductive
enclosure of the apparatus cabinet, or similar,
where the unit is built-in. This conductive
enclosure should be connected to the
earthing system of an installation and may be
directly connected to the protective earth.
Refer to "Safety" section for more information.
15