711S ZONE EXPANSION MODULE
Installation Guide
Figure 1: 711S Zone Expansion Module
DESCRIPTION
The 711S is a flying lead style,
single-zone, addressable expansion
module that allows you to increase
the number of reporting zones
available on DMP panels. Refer to
the panel installation guide for more
information about zone expansion
modules and the maximum number
allowed per panel. The modules
connect to the panel 4-wire Keypad
Bus or LX-Bus™ and are set to
an address that determines the
reporting zone number. The 711S
provides one Type A Class B zone.
Compatibility
All XT30/XT50 and XR150/XR550
Series Panels.
What is Included?
•
711S Expansion Module
•
1k Ohm Resistor
1
ADDRESSING THE 711S MODULE
Setting Address Switches
The 711S Zone Expander uses two rotary switches identified as TENS and
ONES to set the module address. Use a small
screwdriver to set the address accordingly for
Keypad Bus (See Table 1) or LX-bus (See Table 2).
For example, for address 502 on an XR550 Series
panel set the TENS switch to zero and the ONES
switch to two as shown in Figure 2.
Keypad Bus Zone
Numbers
The 711S module uses the first
zone number only. The last three
zone numbers cannot be used
for other devices. For example,
turn the 711S switches to address
02 (TENS = 0, ONES = 2) to set
the module zone number to zone
21. Zones 22, 23, and 24 cannot
be used.
Refer to Table 1 for Keypad Bus
zone numbers and the panels
where they operate.
LX-Bus Zone Numbers
Refer to Table 2 for a partial list of XR550 Series panel LX-Bus zone
numbers. XR150 Series panels only use LX500. For LX-Bus addresses set
the switches to match the last two digits of the address.
LX-Bus
Address
501
506
623
654
742
768
833
877
919
994
2
INSTALLING THE 711S MODULE
The 711S addressable zone expansion module is for use in smaller
applications, such as installing in a pull station back-box or even in a
recessed contact hole behind the contact.
Wiring the 711S Module
Connect the Red, Yellow, Green, and Black wires from the panel Keypad
Bus or LX-Bus™ to the matching wires on the zone expander.
Caution: Do not use looped wire under terminals if wiring directly
to the Keypad bus. Break wire run to provide supervision of
connections.
Keypad
Switches
Address
Tens Ones
1
0
2
0
3
0
4
0
5
0
6
0
7
0
8
0
9
0
10
1
11
1
12
1
13
1
14
1
15
1
16
1
Table 1: Keypad Bus Zone Numbers
LX-Bus
Switches
Number
Tens
1(LX500)
0
1(LX500)
0
2(LX600)
2
2(LX600)
5
3(LX700)
4
3(LX700)
6
4(LX800)
3
4(LX800)
7
5(LX900)
1
5(LX900)
9
Table 2: Example LX-Bus Zone Numbers
TENS
ONES
Figure 2: Switches
Zone Number
XT30/50 XR150
XR550
1
11
11
11
2
21
21
21
3
31
31
31
4
41
41
41
5
51
51
51
6
61
61
61
7
71
71
71
8
81
81
81
9
N/A
N/A
91
0
N/A
N/A
101
1
N/A
N/A
111
2
N/A
N/A
121
3
N/A
N/A
131
4
N/A
N/A
141
5
N/A
N/A
151
6
N/A
N/A
161
Zone
Ones
Number
1
501
6
506
3
623
4
654
2
742
8
768
3
833
7
877
9
919
4
994
Need help?
Do you have a question about the 711S and is the answer not in the manual?