Section 4
Mounting
40
B
C
GUID-17FD88B3-3889-4346-81AD-5D65AC2B0A53 V1 EN
Figure 31:
Drilling holes
A 188 ±1 mm
B ∅ 6.0 mm
C 151 ±1 mm
D 230 ±0.4 mm
E 322 ±0.4 mm
2.
Mount the LHMI and the mounting bracket to the door panel.
2.1. Mount the LHMI with its own installation brackets to the LHMI cutout.
2.2. Mount the mounting bracket to the door panel with the M5 screws.
2.3. Tighten the M5 screws to 4 Nm ±5%.
2.4. Mount the M5 screws in the upper holes of the mounting bracket, but do
not tighten them. Leave them 3...4 mm open.
A
E
1MRS759115 A
D
REX640
Installation Manual