Checking from the fire control panel
The manual call point is installed and electrically connected. See the chapter
'Installation [
25]'.
1. Set the detector line to 'Test' on the fire control panel.
The LED flashes green; this means the detector is in test mode.
2. Push the keyhole cover to the side.
3. Open the door of the manual call point with the key.
4. Press the alarm button.
The test alarm is transmitted. The LED also flashes red by way of
confirmation.
5. Place the key (1) onto the round guide and turn it clockwise so that the black
stopping lever (2) is pushed downward.
The alarm button pops out audibly by approx. 3 mm.
6. Close the door of the manual call point.
7. Close the keyhole cover.
The manual call point is ready for operation again.
8. Check whether an alarm is displayed on the fire control panel.
9. Set the detector line to 'Normal operation' on the fire control panel.
The detector line is ready for operation again.
Checking from the manual call point
You can activate test mode in the fire control panel by opening the door, and
deactivate it by closing the door again. Test mode is only active for a short time.
Therefore, you should work quickly to complete the steps between opening the
door and closing it again. In test mode, the internal alarm indicator flashes green.
Make sure you do not unintentionally activate an alarm.
Please observe the documentation for your fire control panel.
Not every fire control panel allows test mode to be activated automatically. For
some fire control panels, this function must be set explicitly. This setting may be
automatically deactivated under certain circumstances. So that test mode can
also be used from the manual call point with an FC20xx/FC72x fire control panel,
MC link communication, for example, must be active.
Enabling on FC20xx fire control panels
You will find more information for FC20xx fire control panels in 'Enabling detector
exchanger and tester communication' in document number 008838.