Assembling the Product
3
3.9.2 Battery Module Installation
1. Measure the voltage and internal impedance of each module. All modules in one rack frame must be near the
same state of charge. Refer to Table 3-6: Module Voltage and Internal Impedance.
2. Place the battery modules in the rack frame.
Important
Install Battery Modules in the upper shelves first and proceeding to the bottom.
(Two Type B battery modules are inserted in the ninth shelf from the bottom.)
Seventeen battery modules can be inserted into a rack frame as shown in Figure 3-18.
Two Type B Battery
Modules
Figure 3-16: Insertion of Modules on the Ninth Shelf from the Bottom
26
ET003222373
English 4/2018. Rev 0.0