6. Attaching and removing the
unit
6.1 Mounting on IEC rail
6.2 Mounting on the panel
・Dimensions of hole panel(77×45.5)
・Mounting
The panel hole dimensions are as shown below.
Attached to the panel with screws (2pcs).
And it can be attached to a panel of thickness
Tightening torque : 0.63N・m
1.6 – 4.5mm.
Outline of the unit
CL
Mounting screws
CL
Panel
cross recessed head screw with captive washer
Recommended
and flat washer
screws
M3×10
2pcs
67(Unit)
(75)
76
・Panel cut dimensions are made larger than the product
 considering tolerance in panel cut. If you want to prevent dust
 and other intrusion the gap of panel cut, cut the panel
 according to the product to be mounted.
7. How to wire
7.1 Wiring
Follow the wiring diagram for external connections of this unit.
When using this unit, current sensor (EMU-CT50/CT100/CT250/CT400-A/600-A, EMU2-CT5 or EMU2-CT5-4W) is necessary.
1P3W/3P3W (for low voltage circuit)
1P2W (for low voltage circuit)
Fuse : 0.5A
Power source side
Power source side
1
N
1
2
1
2
P1 P2 P3
MA MB
Split-type current sensor
Split-type current sensor
EMU-CT***(50/100/250)
EMU-CT***(50/100/250)
EMU-CT***-A(400/600)
EMU-CT***-A(400/600)
1k 3k 485+ SLD
1L
3L
485-
Ter
K
l
K
l
1L
L
k
1K
L
k
RS485(MODBUS RTU)
Load side
Load side
3P4W (for high voltage circuit)
Power source side
Voltage transformer
Fuse : 0.5A
1
2
3
0
MA MB
P1/P1 P2/P0 P3/P3 NC/P2
Current
transformer ***/ 5A
1k 2k 3k
485+ SLD
X1 Y1
Split-type current sensor
EMU-CT-A
1L 2L 3L
485- Ter COMx COM
Y
Contact/
K
K
l
pulse output
1L
Contact/
L
1K
L
k
Pulse input
K
K
l
2L
L
2K
L
k
RS485(MODBUS RTU)
K
l
K
3L
L
3K
L
k
Load side
* Fuse:P405H (by Daito Communication Apparatus Co., Ltd) equivalent.
* For a low voltage circuit, grounding of the secondary sides of VT (or CT) is not necessary.
・Make sure that before connecting the cable, the orientation of the current sensor is correct for attachment. K to L is the correct direction. K: power source side, L: load side
・EMU-CT50, EMU-CT100, EMU-CT250, EMU-CT400-A,EMU-CT600-A are extendable up to 50m.
・EMU2-CT5, EMU2-CT5-4W are extendable up to 11 m, using together with a extension cable. To extend the wire further, use the current transformer CW-5S(L) for split-type instrument in combination, extending the secondary wiring on
CW-5S(L) side.
・EMU-CT50/100/250/400-A/600-A is used only for low voltage circuit. (Maximum voltage: 460V) It cannot be used for a high voltage circuit. EMU2-CT5 and EMU2-CT5-4W should be used with the secondary side (5A) of transformer transfixed.
If they are used for the circuit directly, they should be used under 200V. (Maximum voltage: 260V)
・Maximum voltage of the circuit connected to this unit directly is 260V for EMU4-BD1-MB, or 277 / 480V for EMU4-HD1-MB. For the circuit over this voltage, use the transformer. Using the transformer, primary voltage is configurable up to
6600V. secondary voltage is fixed to 110V. (special Primary voltage of VT can be set up to 6600V in any, and special secondary voltage of VT can be set up to220V in any.)
・When screwing the terminals at both ends of the terminal block, be careful not to touch the projection of the terminal block cover.
・For MODBUS RTU communication wiring, recommended to have the extra length wires about 200mm (When extended to B / NET transmission from MODBUS RTU communication, use of MODBUS RTU communication wiring is possible).
・Do not ground the secondary side of the current sensor.
*When showing the display part by cutting the panel face in mounting the IEC rail, cut the
panel at where it is more than 50mm away from the fulcrum of the open / close of the door.
・Dimensions of hole panel(77×45.5)
・Mounting
The panel hole dimensions are as shown below.
Mount the unit to mounting plate by mounting screws (M3×10),
And it can be attached to a panel of thickness
then mount the panel mounting attachment.
1.6 – 4.5mm.
Tightening torque : 0.63N・m
Outline of the unit
CL
Mounting screws
Panel mounting
attachment
CL
*Please screw up the panel mounting attachment where there are
high levels of vibration.
*The screws (mounting screws and screws for panel mounting
67(Unit)
attachment) are supplied with panel mounting attachment.
28
(75)
76
106(Attachment)
・Panel cut dimensions are made larger than the product
 considering tolerance in panel cut. If you want to prevent dust
 and other intrusion the gap of panel cut, cut the panel
 according to the product to be mounted.
3P3W (for high voltage circuit)
Fuse: 0.5A
Power source side
Voltage transformer
Fuse : 0.5A
1
2
3
3
3
P1/P1 P2/P0 P3/P3 NC/P2
MA MB
P1 P2 P3
MA MB
Current
transformer ***/ 5A
1k 2k 3k
485+ SLD
1k
3k
485+
SLD
Split-type current sensor
1L 2L 3L
485- Ter COMx COM
EMU-CT-A
1L
3L
485-
Ter
1L
K
K
l
1K
L
L
K
l
k
RS485(MODBUS RTU)
3L
K
K
l
RS485(MODBUS RTU)
3K
L
k
L
L
k
Load side
・For protection against noise, transmission lines and input/output lines shall not be placed close
to or bound together with the power lines and high-voltage lines. Keep distance as below
between them. (except for the terminal block)
Condition
distance
High-voltage line 600V or less
300mm or longer
Caution
Other high-voltage line
600mm or longer
・For the actual usage, connect the FG terminal to ground. (D-type ground: Type 3) Connect it
directly to the ground terminal.
This is being bonded to the conductive part of the product for safety reasons and being
connected to the terminal which is connected the outside protection grounding system.
・Do not connect to FG terminal during the insulation resistance test and pressure test.
7.2 How to connect wires
・Use appropriate crimp-type terminal.
・Use electric wires as below, and tighten the terminal screws by the torque as below.
【EMU4-BD1-MB】
Applicable wire
Tightening
torque
Power supply terminals,
AWG24 - 16 (0.2~1.25mm2)
0.8 N・m
voltage input terminals
(single wire / stranded wire)
Current input terminals,
AWG22 - 16 (0.3~1.25mm2)
0.5 - 0.6N・m
input/ output terminals
(single wire / stranded wire)
【EMU4-HD1-MB】
Applicable wire
Tightening
torque
Power supply terminals,
AWG26 - 14 (0.12~0.2mm2)
0.8 - 1.0 N・m
voltage input terminals
(single wire / stranded wire)
Current input terminals,
AWG22 - 16 (0.3~1.25mm2)
0.5 - 0.6N・m
input/ output terminals
(single wire / stranded wire)
8. Dimensions
●EMU4-BD1-MB
CL
Screws for panel
mounting
67
attachment
4
75
9. Specifications
Panel
Item
Model
Phase-wire system
Measurement item
single-phase 2-wire,
three-phase 3-wire
Voltage
circuit
single-phase 3-wire
(*1)
three-phase 4-wire
Rating
Current circuit
Frequency
Auxiliary power supply rating
Consumption VA(*2)
Transient overvoltage
Measurable circuit count
Input signal type
External input
Rated input
X1 Y1
voltage/current
Y
Contact/
Output signal type
pulse output
Contact/
External output
Rated open/close
Pulse input
voltage/current
Operating temperature
Operating humidity
Storage temperature
Operating altitude
Standard(*3)
Possible combination current sensor for
UL
Possible combination optional unit for UL
*1:The transformer of star-delta connection and delta-star connection can't measure connectly because of the phase shifting.
*2: The maximum value of consumption VA is described.
*3:When combine it with a B/NET Communication Unit(Model:EMU4-CM-B), it becomes out of a conformity standard.
*4: EMU4-LM enables to memorize the data of various quantities related to electricity for a certain period. EMU4-CM-C is communicationunit for CC-Link.
10. Optional devices connectable to this unit
Optional devices connectable to this unit are as follows.
Recommended
crimp-type terminal
Device
For M3 screw of
Optional Unit
B/NET Communication Unit for Energy Measuring Unit
external diameter
below 5.6mm
CC-Link Communication Unit for Energy Measuring Unit
For M3 screw of
CC-Link IE Field Network Basic Communication Unit for Energy Measuring Unit
external diameter
Logging Unit for Energy Measuring Unit
below 5.6mm
For the details of each device and the way to connect, refer to the manual of the device.
Recommended
11. Warranty
crimp-type terminal
For M3.5 screw of
・The warranty is effective until the earlier of 1 year after the date of your purchase or 18 months after manufacturing. Repair shall be charged for the case failures occur due
external diameter
to your intent or fault even during the warranty period.
below 5.6mm
For M3 screw of
・If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired
external diameter
・Our company shall not be liable to compensate for any loss arising from events not attributable to our company, opportunity loss and lost earning of the customer due to failure
below 5.6mm
of the product, and loss, secondary loss, accident compensation, damage to other products besides our products and other operations caused by a special reason regardless
of our company's predictability.
Caution
If an abnormal sound, bad-smelling smoke, fever break out from this unit, switch it off promptly and don't use it
12. Customer Service
HEAD OFFICE: TOKYO BUILDING, 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, Japan
Please refer to "catalog" or "User's manual (Details)" for more details.
●EMU4-HD1-MB
CL
67
15
60
4
75
Specifications
EMU4-BD1-MB
EMU4-HD1-MB
single-phase 2-wire / single-phase 3-wire /
single-phase 2-wire / single-phase 3-wire /
three-phase 3-wire
three-phase 3-wire / three-phase 4-wire
Electric energy (consumption, regeneration), Current, Current
Electric energy (consumption, regeneration), Current,
demand, Voltage, Electric power, Electric power demand, Reactive
Current demand, Voltage, Electric power, Electric power
power, Apparent power, Power factor, Frequency, Harmonic current,
demand, Reactive power, Power factor, Frequency,
Harmonic voltage, Reactive energy, Periodic electric energy, Pulse
Reactive energy, Operating time
count value, Operating time, Equivalent CO
110V, 220V AC
110V, 220V, 440V AC
AC110V (b/w 1- and 2-side, 2- and 3-side),
AC110V (b/w 1- and 2-side, 2- and 3-side),
AC220V(b/w 1- and 3-side)
AC220V(b/w 1- and 3-side)
Non-compliant
Min: AC63.5V/110V, Max: AC277V/480V
50A, 100A, 250A, 400A, 600A AC
(The dedicated split type current sensor is used. Each value refers to the current at the primary side of the current sensor)
5A AC
(The dedicated split type current sensor is used. 5A current sensor is used together with the current transformer (CT), and the
primary-side current is configurable up to 6000A.)
Secondary-side current is up to 66.66mA AC.
50Hz-60Hz
100-240VAC (+10%,-15%), 50Hz-60Hz, Transient overvoltage 4,000V
10VA ( AC110V:9VA,AC220V:10VA)
Measuring circuit: CAT Ⅲ, Auxiliary power supply: CAT Ⅲ.
1 circuit
No voltage a-contact 1 input
None
5V DC 7mA
No voltage a-contact 1 output
None
35V DC 75mA or 24V AC 75mA (Power factor = 1)
-5 - +55℃ (Under the conditions indicated in section 3.1)
30 - 85%RH (No condensation)
-10 - +60℃
2000m or below
EMC: EN61326-1: 2013
UL: UL61010-1
LVD: EN-61010-1: 2010
EMU-CT50/100/250,EMU2-CT5,EMU-CT400-A/600-A
EMU-CT50/100/250,EMU2-CT5,EMU-CT400-A/600-A
EMU4-LM, EMU4-CM-C *4
Model
EMU4-CM-B
EMU4-CM-C
EMU4-CM-CIFB
EMU4-LM
Unit [mm]
15
60
2
Connection terminal
The connecter on the left side of the unit
The connecter on the left side of the unit
The connecter on the left side of the unit
The connecter on the left side of the unit

Advertisement

loading

This manual is also suitable for:

Emu4-hd1-mb