Parameter Description
3.3

Inverter parameters (HW)

P0100
Europe / North America
CStat:
C
P-Group: QUICK
Determines whether power settings (e.g. nominal rating plate power - P0307) are expressed in [kW] or [hp].
The default settings for the nominal rating plate frequency (P0310) and maximum motor frequency (P1082)
are also set automatically here, in addition to reference frequency (P2000).
Possible Settings:
0
Europe [kW],
1
North America [hp], frequency default 60 Hz
2
North America [kW], frequency default 60 Hz
Dependency:
Where:
-
Stop drive first (i.e. disable all pulses) before you change this parameter.
-
P0100 can only be changed when P0010 = 1 (Commissioning mode) via the respective Commissioing
interface (e.g. BOP).
-
Changing P0100 resets all rated motor parameters as well as other parameters that depend on the
rated motor parameters (see P0340 - calculation of motor parameters).
Changing P0100 overwrites the settings of the DIP50/60 switch (location shown in the diagram below):
1. Parameter P0100 has an higher priority than the DIP50/60 switch.
2. However, after the inverter is powered-on again and P0100 < 2, the DIP50/60 setting will take priority
and overwrite P0100.
3. The DIP50/60 switch does not have any effect, if P0100 = 2.
Notice:
P0100 setting 2 (==> [kW], frequency default 60 [Hz]) is not overwritten by the setting of DIP switch 2 (see
diagram above).
P0199

Equipment system number

CStat:
UT
P-Group: -
Equipment system number This parameter has no operation effect.
42
Datatype: U16
Unit: -
Active: first confirm
QuickComm.: Yes
frequency default 50 Hz
Power
cycle
P0100 = 2
?
no
DIP50/60 =
DIP50/60
50 Hz
?
yes
Power in kW
Frequency 50 Hz
P0100 = 0
Datatype: U16
Unit: -
Active: first confirm
QuickComm.: No
Min:
0
Def:
0
Max:
2
Quick
commissioning
P0010 = 1
yes
yes
P0100 = 2
no
P0100 = 1
no
Power in kW
Power in hp
Frequency 60 Hz
Frequency 60 Hz
P0100 = 2
P0100 = 1
Min:
0
Def:
0
Max:
255
MICROMASTER 440
6SE6400-5BB00-0BP0
Issue 01/06
Level
1
?
no
?
yes
Level
2
Parameter List