3 SETUP AND USE
3$*(
'(6&5,37,21
5
RELAY ALARM
LATCHCODE = XX
This setpoint allows the choice of output relay latch attributes. A latched output relay must be manually
reset. An unlatched relay will be automatically reset when the condition that caused the relay activation
goes away.
Note: Trip functions must always be manually reset regardless of the Latchcode value chosen
here. This setpoint allows Alarm functions to be either manually or automatically resetable. The
Immediate O/L Alarm function will always be automatically reset regardless of the Latchcode.
latched = manual reset, unlatched = automatic reset
(see Table 3-6 for complete relay functions/configurations)
For the model 169 Plus:
Value
1
2 or 3
4 or 5
6 or 7
For the model 169:
Value
1 or 4 or 5
2 or 3 or 6 or 7
Factory Value = 1
5
RELAY FAILSAFE
CODE = X
This code allows the choice of output relay fail-safe attributes. FS = fail-safe, NFS = non-fail-safe (see
Glossary). See Table 3-7 for complete relay functions/configurations.
For the model 169 Plus:
Value
Trip
1
FS
2
NFS
3
FS
4
NFS
5
FS
6
NFS
7
FS
8
NFS
For the model 169:
Value
Trip
1 or 5
FS
2 or 6
NFS
3 or 7
FS
4 or 8
NFS
Factory Value = 1
Note: Due to the hardware configuration of the 169/169 Plus drawout relay this code cannot be
changed on any drawout models without corresponding hardware change.
Trip
Alarm
latched
unlatched
latched
latched
latched
unlatched
latched
latched
Trip
Alarm
latched
unlatched
latched
latched
Alarm
Aux. 1 Aux. 2
NFS
NFS
FS (see Figure 2-5)
FS
NFS
FS
FS
NFS
FS
NFS
FS
FS
NFS
FS
FS
FS
FS
FS
FS
FS
FS
NFS
NFS
FS
Alarm
NFS (see Figure 2-5)
FS
FS
NFS
Aux. 1
Aux. 2
unlatched
latched
unlatched
latched
latched
latched
latched
latched
54