3 SETUP AND USE
3$*(
'(6&5,37,21
4
PAGE 4: SETPOINT VALUES
RELAY CONFIGURATION
This page assigns trip and alarm functions to specific output relays (i.e. TRIP, ALARM, AUX. 1, AUX. 2
on the 169 Plus, or TRIP and ALARM on the model 169).
separately to the appropriate relay or to "NO" relay. If an alarm feature is assigned to no relay, it can still
become active (i.e. cause the appropriate alarm message to be displayed if setpoints are exceeded) but
no output relay activation will occur. Possible assignments and factory values are shown below. Only
one TRIP may occur at any one time. TRIP functions must therefore be used to trip the motor.
Once one TRIP function is active, no other trip may occur.
4
Assign XXXXXXXXXXXXXXXX
to XXXXXXXXXXXX relay
For the model 169 Plus:
Feature
O/L TRIP
U/B TRIP
S/C TRIP
RAPID TRIP
STATOR RTD TRIP
RTD TRIP
G/F TRIP
ACCEL. TIME TRIP
PHASE REV. TRIP
STARTS/HOUR TRIP
SPEED SWITCH TRIP
DIFFERENTIAL TRIP
SINGLE PHASE TRIP
SPARE INPUT TRIP
START INHIBIT
O/L WARNING
G/F ALARM
U/B ALARM
U/C ALARM
STATOR RTD ALARM
RTD ALARM
NO SENSOR ALARM
SELF-TEST FAIL
SPARE INPUT ALARM
For the model 169:
Feature
O/L TRIP
U/B TRIP
S/C TRIP
RAPID TRIP
STATOR RTD TRIP
RTD TRIP
G/F TRIP
ACCEL. TIME TRIP
PHASE REV. TRIP
STARTS/HOUR TRIP
SINGLE PHASE TRIP
O/L WARNING
G/F ALARM
U/B ALARM
U/C ALARM
STATOR RTD ALARM
RTD ALARM
NO SENSOR ALARM
SELF-TEST FAIL
Possible Assignments
TRIP or AUX. 1 or TRIP & AUX.1
TRIP or AUX. 1 or TRIP & AUX.1
TRIP or AUX. 1 or TRIP & AUX.1
TRIP or AUX. 1 or TRIP & AUX.1
TRIP or AUX. 1 or TRIP & AUX.1
TRIP or AUX. 1 or TRIP & AUX.1
TRIP or AUX. 1 or TRIP & AUX.1
TRIP or AUX. 1 or TRIP & AUX.1
TRIP or AUX. 1 or TRIP & AUX.1
TRIP or AUX. 1 or TRIP & AUX.1
TRIP or AUX. 1 or TRIP & AUX.1
TRIP or AUX. 1 or TRIP & AUX.1
TRIP or AUX. 1 or TRIP & AUX.1
TRIP or AUX. 1 or TRIP & AUX.1
TRIP or AUX. 1 or TRIP & AUX.1
ALARM or AUX. 1 or AUX. 2 or NO
ALARM or AUX. 1 or AUX. 2 or NO
ALARM or AUX. 1 or AUX. 2 or NO
ALARM or AUX. 1 or AUX. 2 or NO
ALARM or AUX. 1 or AUX. 2 or NO
ALARM or AUX. 1 or AUX. 2 or NO
ALARM or AUX. 1 or AUX. 2 or NO
ALARM or AUX. 1 or AUX. 2 or NO
ALARM or AUX. 1 or AUX. 2 or NO
Possible Assignments
(not shown)
(not shown)
(not shown)
(not shown)
(not shown)
(not shown)
(not shown)
(not shown)
(not shown)
(not shown)
(not shown)
ALARM or NO
ALARM or NO
ALARM or NO
ALARM or NO
ALARM or NO
ALARM or NO
ALARM or NO
ALARM or NO
49
g
Each trip/alarm function is assigned
Factory Value
TRIP RELAY
TRIP RELAY
TRIP RELAY
TRIP RELAY
TRIP RELAY
TRIP RELAY
TRIP RELAY
TRIP RELAY
TRIP RELAY
TRIP RELAY
TRIP RELAY
TRIP RELAY
TRIP RELAY
TRIP RELAY
TRIP RELAY
ALARM RELAY
ALARM RELAY
ALARM RELAY
ALARM RELAY
AUX. 1 RELAY
AUX. 1 RELAY
AUX. 1 RELAY
AUX. 2 RELAY
NO RELAY
Factory Value
TRIP RELAY
TRIP RELAY
TRIP RELAY
TRIP RELAY
TRIP RELAY
TRIP RELAY
TRIP RELAY
TRIP RELAY
TRIP RELAY
TRIP RELAY
TRIP RELAY
ALARM RELAY
ALARM RELAY
ALARM RELAY
ALARM RELAY
ALARM RELAY
ALARM RELAY
ALARM RELAY
ALARM RELAY
GE Power Management

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

169 plus

Table of Contents