Features
Stripped length
Tool
Tightening torque
Max. current carrying capacity, incl. loop-through
Max. cable length
Interface assignments
Table 4-13
Pin
1
2
3
4
Note
The 24 V is looped through via the 24 V connector. In this case, pin 1 is jumpered with pin 2,
and pin 3 is jumpered with pin 4 in the connector. The maximum current can be limited through
the current carrying capacity of the cable. The current carrying capacity of the cable depends,
for example, on the type of cable installation (cable duct, laying on a cable rack, etc.).
SIMOTION D4x5-2
Manual, 04/2014
Flexible, with wire-end ferrule without plastic
sleeve
Flexible, with wire-end ferrule with plastic
sleeve
AWG / kcmil
Power supply X124
Type
0.2 mm² ... 2.5 mm²
0.2 mm² ... 1.5 mm²
22 ... 12
6 ... 7 mm
Screwdriver 0.5 x 3 mm (M2.5)
0.4 to 0.5 Nm
20 A (15 A per UL/CSA)
10 m
Signal name
+
+
G
G
Interfaces
4.5 Power supply
Meaning
Power supply 24 V
Power supply 24 V
Ground
Ground
65