Interfaces
4.3 PROFINET IO interface (only for SIMOTION D4x5-2 DP/PN)
Interface characteristics
Table 4-5
Ports X150 P1 to P3
Characteristic
Connector type
Cable type
Maximum cable length
Minimum transmission cycle
Autocrossing
Dust protection filler plugs for
sealing unused PROFINET ports
Interface assignments
Table 4-6
Assignment of the ports X150 P1 to P3
Representation
Connectable devices
The following devices can be connected to the PROFINET IO interface:
● PG/PC programming devices (communication with SIMOTION SCOUT / STEP 7)
● SIMATIC HMI devices
● SIMATIC controllers with PROFINET interface
● Distributed I/O
● Drive units with PROFINET IO interface (standard devices)
The SIMOTION D4x5‑2 DP/PN then assumes the role of a PROFINET IO controller and can
offer the following functions:
56
Type
RJ45 socket connector
PROFINET
100 m
0.25 ms (D455‑2 DP/PN: 0.125 ms)
Yes
i.e. both crossed and uncrossed cables can be used
5 filler plugs contained in the D4x5‑2 scope of delivery
Filler plugs (50 pcs) order number: 6SL3066‑4CA00‑0AA0
Pin
Name
1
TXP
2
TXN
3
RXP
4
-
5
-
6
RXN
7
-
8
-
Description
Transmit data +
Transmit data -
Receive data +
Reserved, do not use
Reserved, do not use
Receive data -
Reserved, do not use
Reserved, do not use
SIMOTION D4x5-2