Switch-I; Toff - ABB ACS800 Application Manual

Hide thumbs Also See for ACS800:
Table of Contents

Advertisement

28

SWITCH-I

Type
Illustration
Operation
Connections

TOFF

Type
Illustration
Operation
Connections
Function blocks
Logical function
SWITCH-I
I1
I2
O
I3
The output is equal to input I2 if input I1 is true and equal to input I3 if input I1 is
false.
I1
I2
I3
O
0
I2
I3
I3
1
I2
I3
I2
Input I1: Boolean value
Input I2 and I3: 24 bit integer values (23 bits + sign)
Output (O): 24 bit integer value (23 bits + sign)
Timing function
TOFF
I1
O
I2
The output is true when input I1 is true. The output is false when input I1 has been
false for a time equal or longer than input I2.
Input I1
1
0
Output
All bits 1
All bits 0
Values on display: True = -1, false = 0.
Input I1: Boolean value
Input I2: 24 bit integer value (23 bits + sign). One corresponds to 1 ms.
Output (O):
- 24 bit integer value (packed boolean)
Input I2
t
Input I2
t

Hide quick links:

Advertisement

Table of Contents
loading