ABB 07CR41 Operating Manual page 31

Series 40 and 50
Table of Contents

Advertisement

Advant Controller AC 31 / Issued: 01.99
Integrated outputs
- Number of outputs
- Isolated outputs (test voltage)
- Output current/channel
Direct voltage 24 V d.c.
Alternating current 24 to 230 V a.c.
- Total load current
- Output leakage current
- Leakage voltage
- Minimum cut-off values
- Breaking power under 120 V a.c.
(contact rating code B300) (UL)
- Breaking power under 250 V a.c.
(contact rating code B300) (UL)
- Number of groups
- Switching frequency
for resistive loads
for inductive loads
for lamps
- Maximum number of switches:
for AC-1
for AC-15
- Short circuit and overload protection
- Surge voltage protection
- Outputs diagnosis
- Cable length:
unshielded
shielded
ICMK 14 F1
24 V d.c.
6 relays
1500 Vrms
1 min
2 A
2 A AC-1
0.5 A AC-15
6 x 2 A
-
-
10 mA under
12 V d.c.
2 A
2 A (1.5 A
acc. to UL)
2 (2+4)
< 1 Hz
< 0.2 Hz
< 0.2 Hz
1 million
100.000
external
external
-
150 m
500 m
3 – 13
Technical specifications
ICMK 14 F1
ICMK 14 N1
120/230 V a.c.
24 V d.c.
6 relays
6 transistors
1500 Vrms
1500 V a.c.
1 min
2 A
0.5 A
1 A for
Axx,00 and
Axx,01
2 A AC-1
0.5 A AC-15
6 x 2 A
4 x 0.5 A
+ 2 x 1 A
< 200 µA
-
-
0.2 V max.
500 mA
10 mA under
12 V
12 V d.c.
2 A
2 A (1.5 A
acc. to UL)
2 (2+4)
< 1 Hz
< 5 kHz
< 0.2 Hz
< 0.2 Hz
1 million
-
100.000
external
yes: thermic
external
yes:
by transient
voltage
suppression
-
Overload and
short circuit
150 m
150 m
500 m
500 m
3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents