Engineering and remote access
3.5 Cyclic and acyclic data
0x0002: Battery parameters (reading/writing)
Data
Battery defect voltage [0.01 V]
Battery capacity [0.1 Ah]
Ignore battery coding
0x0003: Charging parameters (reading/writing)
Data
End of charge voltage [0.01 V]
Charge current [1 mA]
0x0004: Reset parameters (reading/writing)
Data
Reset time [1 s]
0x0005: Battery information parameters (reading)
Data
Number of batteries
Fill byte(s)
Batt 1: Standby time [1 s]
Batt 1: Buffer time [1 s]
Batt 1: Total charging current
[1 mAh]
Batt 1: Total culled current [1 mAh]
Batt 1: EOCV [0.01 V]
Batt 1: Charge current [1 mA]
94
Description
Battery defect voltage: If the battery voltage falls below the set
value, then the battery is identified to be defective.
Battery capacity: Total battery capacity of all energy storage de-
vices connected to the
SITOP UPS1600.
Ignore data of the coded battery: When this parameter is set to
"1", then data of the coded battery is ignored. Instead, data is
taken from the parameterization ("Battery Parameters", "Charging
Parameters").
Description
End of charge voltage: Battery voltage when charging changes to
trickle charging. The connected energy storage device is then
charged up to 100 %.
Charge current: Current magnitude used to charge the connected
battery modules during the constant charging process.
Description
Reset time: Time during which the SITOP UPS1600 output is
shutdown if the connected devices are reset.
Description
Number of connected battery modules. Here, only the
SITOP UPS1100 battery modules (coded batteries) are counted.
-
Standby time
Required buffer time, after which the SITOP UPS1600 shuts down
in the buffer mode.
Total charge level (battery-specific data): Total charge within the
service lifetime of the SITOP UPS1600.
Total charge level used (battery-specific data): Total discharge
over the lifetime of the SITOP UPS1600.
"End-of-charge voltage": Battery voltage when charging changes
to trickle charging. The energy storage device is then charged up
to 100 %.
Charge current: Current magnitude used to charge the connected
battery modules during the constant charging process.
Data type
Unsigned16
Unsigned16
Unsigned8
Data type
Unsigned16
Unsigned16
Data type
Unsigned8
Data type
Unsigned8
3 x Unsigned8
Unsigned32
Unsigned32
Unsigned32
Unsigned32
Unsigned16
Unsigned16
SITOP UPS1600 / UPS1100
Manual, 04.2017, A5E37775406-8-76