Mitsubishi Electric MELSEC-Q Series Programming Manual page 123

Melsap-l
Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

*6 An initial start is always performed in the Basic model QCPU and the Universal model QCPU with serial number (first five digits) "11042"
or earlier.
*7 The status (ON/OFF) of the output is determined according to the "Output Mode at STOP to RUN" setting in PLC parameter.
• When the programmable controller is powered OFF or the CPU module is reset, the intelligent function
modules and special function modules are initialized. When making a resume start, create an initial program
for the intelligent function module/special function module in the block that is always active or in the
sequence program.
• When the programmable controller is powered OFF or the CPU module is reset, values in the devices
without a latch setting are cleared. To hold the values in the SFC information devices, set a latch range.
4 SFC PROGRAM CONFIGURATION
4.7 SFC Operation Mode Setting
4
121

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec-l series

Table of Contents