Siemens SIPROTEC 5 Manual page 326

Fault recorder, v7.50 and higher
Hide thumbs Also See for SIPROTEC 5:
Table of Contents

Advertisement

Fault Recorder
7.5 Trigger Functions 3-Phase
Addr.
_:9751:116
General
_:9781:1
_:9781:117
_:9781:112
Max. trigger
_:9781:101
_:9781:105
_:9781:118
_:9781:119
_:9781:120
_:9781:113
Min. trigger
_:9781:102
_:9781:106
326
Parameter
C
Trig. I fund 1:-dM/dt
hysteresis
Trig. I RMS 1:Mode
Trig. I RMS 1:Phase-
selective
Trig. I RMS 1:Filter time
Trig. I RMS 1:Max. active
Trig. I RMS 1:Max. (Non-
1 A @ 100 Irated 0.030 A to 100.000 A
phs sel.)
5 A @ 100 Irated 0.15 A to 500.00 A
1 A @ 50 Irated
5 A @ 50 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
Trig. I RMS 1:Max. phs A 1 A @ 100 Irated 0.030 A to 100.000 A
5 A @ 100 Irated 0.15 A to 500.00 A
1 A @ 50 Irated
5 A @ 50 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
Trig. I RMS 1:Max. phs B 1 A @ 100 Irated 0.030 A to 100.000 A
5 A @ 100 Irated 0.15 A to 500.00 A
1 A @ 50 Irated
5 A @ 50 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
Trig. I RMS 1:Max. phs C 1 A @ 100 Irated 0.030 A to 100.000 A
5 A @ 100 Irated 0.15 A to 500.00 A
1 A @ 50 Irated
5 A @ 50 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
Trig. I RMS 1:Max. hyste-
resis
Trig. I RMS 1:Min. active
Trig. I RMS 1:Min. (Non-
1 A @ 100 Irated 0.030 A to 100.000 A
phs sel.)
5 A @ 100 Irated 0.15 A to 500.00 A
1 A @ 50 Irated
5 A @ 50 Irated
1 A @ 1.6 Irated
5 A @ 1.6 Irated
Setting Options
0.900 p.u. to 0.990 p.u.
off
on
test
no
yes
2 cycles to 250 cycles
no
yes
0.030 A to 50.000 A
0.15 A to 250.00 A
0.001 A to 1.600 A
0.005 A to 8.000 A
0.030 A to 50.000 A
0.15 A to 250.00 A
0.001 A to 1.600 A
0.005 A to 8.000 A
0.030 A to 50.000 A
0.15 A to 250.00 A
0.001 A to 1.600 A
0.005 A to 8.000 A
0.030 A to 50.000 A
0.15 A to 250.00 A
0.001 A to 1.600 A
0.005 A to 8.000 A
0.900 p.u. to 0.990 p.u.
no
yes
0.030 A to 50.000 A
0.15 A to 250.00 A
0.001 A to 1.600 A
0.005 A to 8.000 A
SIPROTEC 5, Fault Recorder, Manual
C53000-G5040-C018-5, Edition 11.2017
Default Setting
0.980 p.u.
off
no
2 cycles
yes
1.200 A
6.00 A
1.200 A
6.00 A
1.200 A
6.000 A
1.200 A
6.00 A
1.200 A
6.00 A
1.200 A
6.000 A
1.200 A
6.00 A
1.200 A
6.00 A
1.200 A
6.000 A
1.200 A
6.00 A
1.200 A
6.00 A
1.200 A
6.000 A
0.980 p.u.
yes
0.800 A
4.00 A
0.800 A
4.00 A
0.800 A
4.000 A

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siemens 7ke85

Table of Contents