GE T60 Instruction Manual page 596

Transformer protection system
Hide thumbs Also See for T60:
Table of Contents

Advertisement

TRANSDUCER INPUTS/OUTPUTS
It is recommended to use the T60 to configure the RRTD parameters. If the RRTDPC software is used to change the RRTD
settings directly (the application and type settings), then one of the following two operations is required for changes to be
reflected in the T60:
Cycle power to the T60
Break then re-establish the communication link between the RRTD unit and the T60. This causes the RRTD COMM FAIL
operand to be asserted then de-asserted.
5.10.3.2 Remote RTDs 1 through 12
SETTINGS  TRANSDUCER I/O  RRTD INPUTS  RRTD RTD 1(12)
 RRTD 1
5
The remote RTD inputs convert values of input resistance into temperature for further operations. These inputs are
intended to be connected to any of the RTD types in common use. Hardware details are contained in chapter 3.
On power up, the T60 reads and saves all application and type settings from the RRTD. This synchronizes the RRTD and T60.
Any changes to RRTD settings (function, application, or type) from the T60 interface are immediately reflected in the RRTD.
The following rules are followed:
If the
RRTD 1 FUNCTION
If the
RRTD 1 FUNCTION
If the
RRTD 1 APPLICATION
device
If the
RRTD 1 APPLICATION
5-378
RRTD 1 FUNCTION:
Disabled
RRTD 1 ID:
RRTD 1
RRTD 1 TYPE:
100 Ω Platinum
RRTD 1
APPLICATION: None
RRTD 1 ALARM
TEMPERATURE: 130°C
RRTD 1 ALARM
PKP DELAY: 5 s
RRTD 1 TRIP
TEMPERATURE: 130°C
RRTD 1 TRIP
PKP DELAY: 5 s
RRTD 1 TRIP
RST DELAY: 5 s
RRTD 1 TRIP VOTING:
None
RRTD 1 OPEN:
None
RRTD 1 BLOCK:
Off
RRTD 1 TARGET:
Self-reset
RRTD 1 EVENTS:
Disabled
setting is "Enabled," then the
setting is "Disabled," then
RRTD1 APPLICATION
or
settings are changed, then these settings are immediately written to the RRTD
RRTD 1 TYPE
setting is "Group 1" or "Group 2," then a value of "Other" is written to the RRTD device
Range: Disabled, Enabled
Range: Up to 20 alphanumeric characters
Range: 100 Ω Nickel, 10 Ω Copper, 100 Ω Platinum,
120 Ω Nickel
Range: None, Stator, Bearing, Ambient, Group 1,
Group 2
Range: 1 to 200°C in steps of 1
Range: 5 to 600 s in steps of 5
Range: 1 to 200°C in steps of 1
Range: 5 to 600 s in steps of 5
Range: 5 to 600 s in steps of 5
Range: None, Group, Remote RTD 1, Remote RTD 2,...,
Remote RTD 12
Range: None, Alarm, Block
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
setting value is written to RRTD device
RRTD 1 APPLICATION
setting value is set as "None"
T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS

Advertisement

Table of Contents
loading

Table of Contents