GE T60 Instruction Manual page 380

Transformer protection system
Hide thumbs Also See for T60:
Table of Contents

Advertisement

SYSTEM SETUP
5
The breaker control element contains the auxiliary logic for status and serves as the interface for opening and closing of a
circuit breaker from protection, autoreclose, SCADA, or through the front panel interface. The breaker control element can
be used to create interlocking functionality. For greater security in determination of the breaker position, both the 52/a and
52/b auxiliary contacts are used with reporting of the discrepancy between them.
To use this element, configure the contact outputs that trip and close the breaker to use FlexLogic operands
(or
CMD
BREAKER 1 TRIP A/B/C
element inputs as described here.
A description of the operation of the breaker control and status monitoring features from the front panel is provided in
chapter 4.
There are two breaker control elements for each CT/VT module installed. The following settings are available for each
breaker control element.
BREAKER 1 FUNCTION
BREAKER1 PUSH BUTTON CONTROL
BREAKER1 TAGGING
operations are disabled: pushbutton open/close, IEC 61850 open/close, and close command initiated by
setting. The trip command issued by the Trip Out element or
BREAKER1 SUBSTITUTN
breaker 1 control open/close status is forced to the substituted value.
— Set to "Enable" to allow the graphical front panel to bypass breaker 1 interlocking. When asserted,
BREAKER1 BYPASS
BREAKER 1 BLK OPEN
5-162
BREAKER1 ΦA/3P CLSD:
Off
BREAKER1 ΦA/3P OPND:
Off
BREAKER 1 ΦB CLOSED:
Off
BREAKER 1 ΦB OPENED:
Off
BREAKER 1 ΦC CLOSED:
Off
BREAKER 1 ΦC OPENED:
Off
BREAKER 1 TOPERATE:
70 ms
BREAKER 1 EXT ALARM:
Off
BREAKER 1 ALARM
DELAY:
MANUAL CLOSE RECAL1
TIME:
BREAKER 1 OPEN
SEAL-IN:
BREAKER 1 OUT OF SV:
Off
BREAKER 1 RACKED-IN:
Off
BREAKER 1 EVENTS:
Disabled
in the case of single-pole tripping) and
— This setting enables and disables the operation of the breaker 1 control feature.
— Set to "Enable" to allow front panel pushbutton open/close control operations.
— Set to "Enable" to allow the graphical front panel to tag breaker 1. When tagged, the following
— Set to "Enable" to allow the graphical front panel to substitute breaker 1 status. When substituted,
and
settings are bypassed.
BREAKER 1 BLK CLOSE
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: 0 to 65535 s in steps of 1
Range: FlexLogic operand
Range: 0.000 to 65.535 s in steps of 0.001
0.000 s
Range: 0.000 to 65.535 s in steps of 0.001
0.000 s
Range: 0.000 to 65.535 s in steps of 0.001
0.000 s
Range: FlexLogic operand
Range: FlexLogic operand
Range: Disabled, Enabled
BREAKER 1 ON
setting is not affected.
BREAKER 1 OPEN
T60 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
BREAKER 1 OFF
CMD, and configure the breaker control
BREAKER 1 CLOSE