Siemens SINAMICS G120 Operating Instructions Manual page 165

Low voltage converters built-in and wall mounting units with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Motors without motor code stamped on the rating plate:
● INDUCT: Third-party induction motor
● 1L... IND: 1LE1, 1LG6, 1LA7, 1LA9 induction motors
Motors with motor code stamped on the rating plate:
● 1LE1 IND 100: 1LE1 . 9
● 1PC1 IND: 1PC1
● 1PH8 IND: Induction motor
● 1FP1: Reluctance motor
Depending on the inverter, the motor list in BOP-2 can deviate from the list shown above.
If you have selected a motor type with motor code, you must now enter the motor code. The
inverter assigns the following motor data corresponding to the motor code.
If you do not know the motor code, then you must set the motor code = 0, and enter motor
data from p0304 and higher from the rating plate.
87 Hz motor operation The BOP-2 only indicates this step if you selected IEC as the motor
standard (EUR/USA, P100 = KW 50HZ).
Rated motor voltage
Rated motor current
Rated motor power
Rated motor frequency
Rated motor speed
Motor cooling:
● SELF: Natural cooling
● FORCED: Forced-air cooling
● LIQUID: Liquid cooling
● NO FAN: Without fan
Select the application:
● OP LOOP: Recommended setting for standard applications.
● CL LOOP: Recommended setting for applications with short ramp-up and ramp-down times.
● HVY LOAD: Recommended setting for applications with a high break loose torque.
The BOP-2 does not display this step for a PM330 Power Module.
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE
5.4 Quick commissioning using the BOP-2 operator panel
Commissioning
165

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120p

Table of Contents