GE 489 Communications Manual page 52

Generator management relay
Hide thumbs Also See for 489:
Table of Contents

Advertisement

48
Table CG–2: Data Formats (Sheet 7 of 14)
CODE
TYPE
Unsigned
OVERCURRENT CURVE STYLE SELECTION
16 bit integer
0
ANSI Extremely Inverse
1
ANSI Very Inverse
2
ANSI Normally Inverse
3
ANSI Moderately Inverse
4
IEC Curve A (BS142)
5
IEC Curve B (BS142)
F128
6
IEC Curve C (BS142)
7
IEC Short Inverse
8
IAC Extremely Inverse
9
IAC Very Inverse
10
IAC Inverse
11
IAC Short Inverse
12
FlexCurve™
13
Definite Time
Unsigned
ANALOG INPUT SELECTION
16 bit integer
0
Disabled
F129
1
4 to 20 mA
2
0 to 20 mA
3
0 to 1 mA
Unsigned
PICKUP TYPE
16 bit integer
F130
0
Over
1
Under
Unsigned
INPUT SWITCH STATUS
16 bit integer
FC131
0
Closed
1
Open
Unsigned
TRIP COIL SUPERVISION STATUS
16 bit integer
F132
0
No Coil
1
Coil
Unsigned
GENERATOR STATUS
16 bit integer
0
Offline
1
Offline
F133
2
Online
3
Overload
4
Tripped
Unsigned
CAUSE OF EVENT /
16 bit integer
CAUSE OF LAST TRIP
0
No Event
1
General Switch A Trip
2
General Switch B Trip
F134
3
General Switch C Trip
4
General Switch D Trip
5
General Switch E Trip
6
General Switch F Trip
7
General Switch G Trip
489 GENERATOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
DEFINITION

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents