GE 489 Communications Manual page 17

Generator management relay
Hide thumbs Also See for 489:
Table of Contents

Advertisement

CG.3.5 Dual Setpoints
CG.3.6 Passcode Operation
CG.3.7 489 Memory Map
ADDR
PRODUCT ID
0000
GE Multilin Product Device Code
0001
Product Hardware Revision
0002
Product Software Revision
0003
Product Modification Number
0010
Boot Program Revision
0011
Boot Program Modification Number
MODEL ID
0040
Order Code
0050
489 Revision
0060
489 Boot Revision
COMMANDS
0080
Command Function Code (always 5)
0081
Command Operation Code
0088
Communications Port Passcode
00F0
Time (Broadcast)
00F2
Date (Broadcast)
USER_MAP / USER MAP VALUES
0100
User Map Value #1 of 125...
017C
User Map Value #125 of 125
USER_MAP / USER MAP ADDRESSES
0180
User Map Address #1 of 125
0181
User Map Address #2 of 125
0182
User Map Address #3 of 125
...
...
01FC
User Map Address #125 of 125
STATUS / GENERATOR STATUS
0200
Generator Status
0201
Generator Thermal Capacity Used
0202
Estimated Trip Time On Overload
0203
Communications Setpoint Access
1, 2, 3
See Table footnotes on page page 42
489 GENERATOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
Each communications port can individually select an Edit Setpoint Group of interest by
writing address 1342h. This way the front port, rear port and auxiliary port can read and
alter different setpoints simultaneously.
Each communications port can individually set the Passcode Access by writing address
88h with the correct Passcode. This way the front port, rear port and auxiliary port have
individual access to the setpoints. Reading address 0203h,
register, provides the user with the current state of access for the given port. A
ACCESS
value of 1 read from this register indicates that the user has full access rights to changing
setpoints from the given port.
The 489 memory map is shown in the following table.
Table CG–1: 489 Memory Map (Sheet 1 of 30)
Name
RANGE
STEP
N/A
N/A
1 to 26
1
N/A
N/A
0 to 999
1
N/A
N/A
0 to 999
1
0 to 16
1
12
1
12
1
5
N/A
0 to 65535
1
0 to 99999999
1
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
0 to 3FFF
1
0 to 3FFF
1
0 to 3FFF
1
...
...
0 to 3FFF
1
0 to 4
1
0 to 100
1
*
1
0 to 65535
0 to 1
N/A
COMMUNICATIONS SETPOINT
UNITS
FORMAT
DEFAULT
N/A
F1
32
N/A
F15
N/A
N/A
F16
N/A
N/A
F1
N/A
N/A
F16
N/A
N/A
F1
N/A
N/A
F22
N/A
N/A
F22
N/A
N/A
F22
N/A
N/A
F1
N/A
N/A
F1
N/A
N/A
F12
0
N/A
F24
N/A
N/A
F18
N/A
N/A
F1
N/A
N/A
F1
N/A
hex
F1
200
hex
F1
201
hex
F1
202
...
...
...
hex
F1
27C
F133
1
%
F1
0
s
F12
–1
N/A
F126
N/A
13