GE T60 Instruction Manual page 674

Ur series transformer protection system
Hide thumbs Also See for T60:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 70 of 73)
ADDR
REGISTER NAME
D764
...Repeated for Contact Output 61
D773
...Repeated for Contact Output 62
D782
...Repeated for Contact Output 63
D791
...Repeated for Contact Output 64
DCmA Inputs (Read/Write Setting) (24 modules)
B
D7A0
DCmA Inputs 1 Function
D7A1
DCmA Inputs 1 ID
D7A7
Reserved 1 (4 items)
D7AB
DCmA Inputs 1 Units
D7AE
DCmA Inputs 1 Range
D7AF
DCmA Inputs 1 Minimum Value
D7B1
DCmA Inputs 1 Maximum Value
D7B3
...Repeated for DCmA Inputs 2
D7C6
...Repeated for DCmA Inputs 3
D7D9
...Repeated for DCmA Inputs 4
D7EC
...Repeated for DCmA Inputs 5
D7FF
...Repeated for DCmA Inputs 6
D812
...Repeated for DCmA Inputs 7
D825
...Repeated for DCmA Inputs 8
D838
...Repeated for DCmA Inputs 9
D84B
...Repeated for DCmA Inputs 10
D85E
...Repeated for DCmA Inputs 11
D871
...Repeated for DCmA Inputs 12
D884
...Repeated for DCmA Inputs 13
D897
...Repeated for DCmA Inputs 14
D8AA
...Repeated for DCmA Inputs 15
D8BD
...Repeated for DCmA Inputs 16
D8D0
...Repeated for DCmA Inputs 17
D8E3
...Repeated for DCmA Inputs 18
D8F6
...Repeated for DCmA Inputs 19
D909
...Repeated for DCmA Inputs 20
D91C
...Repeated for DCmA Inputs 21
D92F
...Repeated for DCmA Inputs 22
D942
...Repeated for DCmA Inputs 23
D955
...Repeated for DCmA Inputs 24
DNP/IEC Points (Read/Write Setting)
D968
DNP/IEC 60870-5-104 Binary Input Points (256 items)
DB68
DNP/IEC 60870-5-104 Analog Input Points (256 items)
Synchrocheck (Read/Write Setting) (4 modules)
DC70
Synchrocheck 1 Function
DC71
Synchrocheck 1 V1 Source
DC72
Synchrocheck 1 V2 Source
DC73
Synchrocheck 1 Maximum Voltage Difference
DC75
Synchrocheck 1 Maximum Angle Difference
DC76
Synchrocheck 1 Maximum Frequency Difference
DC77
Synchrocheck 1 Dead Source Select
DC78
Synchrocheck 1 Dead V1 Maximum Voltage
DC79
Synchrocheck 1 Dead V2 Maximum Voltage
DC7A
Synchrocheck 1 Live V1 Minimum Voltage
DC7B
Synchrocheck 1 Live V2 Minimum Voltage
DC7C
Synchrocheck 1 Target
DC7D
Synchrocheck 1 Events
DC7E
Synchrocheck 1 Block
DC80
Synchrocheck 1 Frequency Hysteresis
B-78
RANGE
0 to 1
---
0 to 65535
---
0 to 6
-9999.999 to 9999.999
-9999.999 to 9999.999
0 to 4294967295
0 to 65535
0 to 1
0 to 5
0 to 5
0 to 400000
0 to 100
0 to 2
0 to 5
0 to 1.25
0 to 1.25
0 to 1.25
0 to 1.25
0 to 2
0 to 1
0 to 4294967295
0 to 0.1
T60 Transformer Protection System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F102
---
---
F205
---
1
F001
---
---
F206
---
1
F173
---
0.001
F004
---
0.001
F004
---
1
F300
---
1
F600
---
1
F102
---
1
F167
---
1
F167
V
1
F060
degrees
1
F001
Hz
0.01
F001
---
1
F176
1 (LV1 and DV2)
pu
0.01
F001
pu
0.01
F001
pu
0.01
F001
pu
0.01
F001
---
1
F109
---
1
F102
---
1
F300
Hz
0.01
F001
DEFAULT
0 (Disabled)
"DCMA Ip 1"
0
"mA"
6 (4 to 20 mA)
4000
20000
0
0
0 (Disabled)
0 (SRC 1)
1 (SRC 2)
10000
30
100
30
30
70
70
0 (Self-reset)
0 (Disabled)
0
6
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents