GE T60 Instruction Manual page 550

Ur series transformer protection system
Hide thumbs Also See for T60:
Table of Contents

Advertisement

9.2 DIFFERENTIAL CHARACTERISTIC TEST EXAMPLES
TEST
PHASE
Slope 2
Slope 2
9
9-12
INJECTED CURRENT
W1 CURRENT
W2 CURRENT
A
0 ∠0°
0.315 ∠–90°
8.33 ∠–270°
B
0.315 ∠–270°
8.33 ∠–90°
C
0 ∠0°
A
B
0.18 ∠–90°
8.33 ∠–270°
C
0.18 ∠–270°
8.33 ∠–90°
T60 Transformer Protection System
DISPLAYED CURRENT
DIFFERENTIAL
0 ∠0°
0 ∠0°
7.77 ∠–270°
7.77 ∠–90°
0 ∠0°
0 ∠0°
8 ∠–270°
8 ∠–90°
9 COMMISSIONING
STATUS
RESTRAINT
0 ∠0°
Block
I
I
/
= 93.2%
d
r
8.33 ∠–270°
< Slope 2 = 95%
8.33 ∠–90°
0 ∠0°
Operate
I
I
/
= 96%
d
r
8.33 ∠–270°
> Slope 2 = 95%
8.33 ∠–90°
GE Multilin