5 SETTINGS
Table 5–20: T60 FLEXLOGIC OPERANDS (Sheet 5 of 9)
OPERAND TYPE
OPERAND SYNTAX
ELEMENT:
PMU Agg 1 SvEng On
Synchrophasor
PMU 1 CURR TRIGGER
phasor
PMU 1 FREQ TRIGGER
measurement unit
PMU 1 POWER TRIGGER
(PMU)
PMU 1 ROCOF TRIGGER
PMU 1 VOLT TRIGGER
PMU 1 TRIGGERED
ELEMENT:
PMU ONE-SHOT EXPIRED
Synchrophasor one-
shot
PMU ONE-SHOT OP
PMU ONE-SHOT PENDING
ELEMENT:
POWER SWING OUTER
Power swing detect
POWER SWING MIDDLE
POWER SWING INNER
POWER SWING BLOCK
POWER SWING TMR2 PKP
POWER SWING TMR3 PKP
POWER SWING TMR4 PKP
POWER SWING TRIP
POWER SWING 50DD
POWER SWING INCOMING
POWER SWING OUTGOING
POWER SWING UN/BLOCK
ELEMENT:
RESTD GND FT1 PKP
Restricted ground
RESTD GND FT1 OP
fault
RESTD GND FT1 DPO
RESTD GND FT2 to 6
ELEMENT:
RRTD COMM FAIL
Remote RTD
RRTD RTD 1 ALARM DPO
protection
RRTD RTD 1 ALARM OP
RRTD RTD 1 ALARM PKP
RRTD RTD 1 OPEN
RRTD RTD 1 SHORTED
RRTD RTD 1 TRIP DPO
RRTD RTD 1 TRIP OP
RRTD RTD 1 TRIP PKP
RRTD RTD 2 to 12
ELEMENT:
SELECTOR 1 POS Y
Selector switch
SELECTOR 1 BIT 0
SELECTOR 1 BIT 1
SELECTOR 1 BIT 2
SELECTOR 1 STP ALARM
SELECTOR 1 BIT ALARM
SELECTOR 1 ALARM
SELECTOR 1 PWR ALARM
SELECTOR 2
ELEMENT:
SETTING GROUP ACT 1
Setting group
SETTING GROUP ACT 2
SETTING GROUP ACT 3
SETTING GROUP ACT 4
SETTING GROUP ACT 5
SETTING GROUP ACT 6
ELEMENT:
SRC1 50DD OP
Disturbance
SRC2 50DD OP
detector
SRC3 50DD OP
SRC4 50DD OP
SRC5 50DD OP
SRC6 50DD OP
GE Multilin
OPERAND DESCRIPTION
SvEng data item in associated control block is on
Overcurrent trigger of phasor measurement unit 1 has operated
Abnormal frequency trigger of phasor measurement unit 1 has operated
Overpower trigger of phasor measurement unit 1 has operated
Rate of change of frequency trigger of phasor measurement unit 1 has
operated
Abnormal voltage trigger of phasor measurement unit 1 has operated
Phasor measurement unit 1 triggered; no events or targets are generated by
this operand
Indicates the one-shot operation has been executed, and the present time is
at least 30 seconds past the scheduled one-shot time
Indicates the one-shot operation and remains asserted for 30 seconds
afterwards
Indicates the one-shot operation is pending; that is, the present time is before
the scheduled one-shot time
Positive-sequence impedance in outer characteristic
Positive-sequence impedance in middle characteristic
Positive-sequence impedance in inner characteristic
Power swing blocking element operated
Power swing timer 2 picked up
Power swing timer 3 picked up
Power swing timer 4 picked up
Out-of-step tripping operated
The power swing element detected a disturbance other than power swing
An unstable power swing has been detected (incoming locus)
An unstable power swing has been detected (outgoing locus)
Asserted when power swing is detected and de-asserted when a fault during
power swing occurs
Restricted ground fault 1 has picked up
Restricted ground fault 1 has operated
Restricted ground fault 1 has dropped out
Same set of operands as shown for RESTD GND FT1
Asserted when RRTD loss of communications is detected
Asserted when the RRTD RTD 1 alarm stage drops out
Asserted when the RRTD RTD 1 alarm stage operates
Asserted when the RRTD RTD 1 alarm stage picks up
Asserted when the RRTD RTD 1 detects an open circuit
Asserted when the RRTD RTD 1 detects an short/low circuit
Asserted when the RRTD RTD 1 trip stage drops out
Asserted when the RRTD RTD 1 trip stage operates
Asserted when the RRTD RTD 1 trip stage picks up
Same set of operands as shown
Selector switch 1 is in Position Y (mutually exclusive operands)
First bit of the 3-bit word encoding position of selector 1
Second bit of the 3-bit word encoding position of selector 1
Third bit of the 3-bit word encoding position of selector 1
Position of selector 1 has been pre-selected with the stepping up control
input but not acknowledged
Position of selector 1 has been pre-selected with the 3-bit control input but
not acknowledged
Position of selector 1 has been pre-selected but not acknowledged
Position of selector switch 1 is undetermined or restored from memory when
the relay powers up and synchronizes to the three-bit input
Same set of operands as shown above for SELECTOR 1
Setting group 1 is active
Setting group 2 is active
Setting group 3 is active
Setting group 4 is active
Setting group 5 is active
Setting group 6 is active
Source 1 disturbance detector has operated
Source 2 disturbance detector has operated
Source 3 disturbance detector has operated
Source 4 disturbance detector has operated
Source 5 disturbance detector has operated
Source 6 disturbance detector has operated