Commands - GE 345 Communications Manual

Transformer protection system transformer protection and control
Hide thumbs Also See for 345:
Table of Contents

Advertisement

RS485 INTERFACE

Commands

1–24
Modbus Address
Description
44384
First ASDU Identification Type
44385
First ASDU Function Type
44386
First ASDU Information Number
44387
First ASDU Scan Timeout
44388
First ASDU First Analog Entry
44389
First ASDU First Analog Factor
44390
First ASDU First Analog Offset
44391
First ASDU Second Analog Entry
44392
First ASDU Second Analog Factor
44393
First ASDU Second Analog Offset
...
...
44412
First ASDU Ninth Analog Entry
44413
First ASDU Ninth Analog Factor
...
...
44443
Second ASDU Ninth Analogue Entry
44444
Second ASDU Ninth Analogue Factor
44445
Second ASDU Ninth Analogue Offset
...
...
44446
Third ASDU Identification Type
...
...
44476
Third ASDU Ninth Analogue Offset
In the measurands configuration screen, with each selected measurement, a Factor and
an Offset must be configured.
The Factor is a multiplier factor.
The Offset is an offset factor to be applied to the relay measurement to make the final
measurement calculation to be sent to the master
The factor and offset parameters allow the user to perform different scaling in the relay
measurements. The final measurement sent to the IEC103 master will be: "a*x+b", where
"x" is the relay measurement, "a" is the multiplier factor and "b" is the offset.
The measurands will be sent to the primary station as a response to a class 2 request.
There is a Timeout configurable with increments of 100 ms, between 0 and 60 min, in order
to configure the desired interval.
All the commands and virtual inputs are available to be mapped using the EnerVista Setup
program. It is possible to choose the desired command for the ON state and the same or
different command for the OFF state.
The user is able to select the Information Number <1..255> and the Function Type <0..255>
command mappings, but the Identification Type 20 (General Commands) is fixed.++ There
are 32 configurable commands.
In this case it will be necessary to define a new format.
For example, FC500:
CHAPTER 1: COMMUNICATIONS GUIDE
345 TRANSFORMER PROTECTION SYSTEM – COMMUNICATIONS GUIDE
Value
Format
3 or 9
F1
<0 – 255 >
F1
< 0 – 255 >
F1
< 0 – 1000> secs
F1
Vab
F1
1
F3
0
F1
Ib
F1
1
F3
0
F1
...
...
Ib
F1
1
F3
...
...
...
...
...
...

Advertisement