value. It is a basic arithmetic function that can be used for
monitoring, supervision, interlocking and other logics.

14. Monitoring

Measurements CVMMXN, CMMXU, VNMMXU, VMMXU,
CMSQI, VMSQI
The measurement functions are used to get on-line
information from the IED. These service values make it
possible to display on-line information on the local HMI and
on the substation automation system about:
• measured voltages, currents, frequency, active, reactive
and apparent power and power factor
• measured analog values from merging units
• primary phasors
• positive, negative and zero sequence currents and
voltages
• mA, input currents
• pulse counters

Supervision of mA input signals

The main purpose of the function is to measure and process
signals from different measuring transducers. Many devices
used in process control represent various parameters such as
frequency, temperature and DC battery voltage as low current
values, usually in the range 4-20 mA or 0-20 mA.
Alarm limits can be set and used as triggers, e.g. to generate
trip or alarm signals.
The function requires that the IED is equipped with the mA
input module.

Disturbance report DRPRDRE

Complete and reliable information about disturbances in the
primary and/or in the secondary system together with
continuous event-logging is accomplished by the disturbance
report functionality.
Disturbance report (DRPRDRE), always included in the IED,
acquires sampled data of all selected analog input and binary
signals connected to the function block with a maximum of
40 analog and 352 binary signals.
The Disturbance report functionality is a common name for
several functions:
• Event list
• Indications
• Event recorder
• Trip value recorder
• Disturbance recorder
• Fault locator
• Settings information
36
The Disturbance report function is characterized by great
flexibility regarding configuration, starting conditions,
recording times, and large storage capacity.
A disturbance is defined as an activation of an input to the
AnRADR or BnRBDR function blocks, which are set to trigger
the disturbance recorder. All connected signals from start of
pre-fault time to the end of post-fault time will be included in
M12024-3 v9
the recording. Disturbance record will have visible settings
from all function instances that are configured in the
application configuration tool.
Every disturbance report recording is saved in the IED in the
standard Comtrade format as a reader file HDR, a
configuration file CFG, and a data file DAT. The same applies
to all events, which are continuously saved in a ring-buffer.
The local HMI is used to get information about the recordings.
The disturbance report files can be uploaded to PCM600 for
further analysis using the disturbance handling tool.

Event list DRPRDRE

Continuous event-logging is useful for monitoring the system
from an overview perspective and is a complement to specific
M16054-3 v2
disturbance recorder functions.
The event list logs all binary input signals connected to the
Disturbance recorder function. The list may contain up to
1000 time-tagged events stored in a ring-buffer.
Indications DRPRDRE
To get fast, condensed and reliable information about
disturbances in the primary and/or in the secondary system it
is important to know, for example binary signals that have
changed status during a disturbance. This information is used
in the short perspective to get information via the local HMI in
a straightforward way.
M12153-3 v13
There are three LEDs on the local HMI (green, yellow and
red), which will display status information about the IED and
the Disturbance recorder function (triggered).
The Indication list function shows all selected binary input
signals connected to the Disturbance recorder function that
have changed status during a disturbance.
Event recorder DRPRDRE
Quick, complete and reliable information about disturbances
in the primary and/or in the secondary system is vital, for
example, time-tagged events logged during disturbances.
This information is used for different purposes in the short
term (for example corrective actions) and in the long term (for
example functional analysis).
The event recorder logs all selected binary input signals
connected to the Disturbance recorder function. Each
recording can contain up to 150 time-tagged events.
The event recorder information is available for the
disturbances locally in the IED.
1MRK 511 404-BEN A
M12412-6 v8
M12030-3 v6
M12033-3 v8