Bay control REC670 2.2
Product version: 2.2.1
Inverse characteristic
Table 155. ANSI Inverse time characteristics
Function
Operating characteristic:
æ
ö
A
ç
÷
=
+
× +
t
B k tDef
(
)
ç
÷
P
ç
-
÷
I
1
è
ø
EQUATION1249-SMALL V2 EN-US
Reset characteristic:
t r
=
×
t
k
(
)
2
-
I
1
EQUATION1250-SMALL V1 EN-US
I = I
/I
measured
set
ANSI Extremely Inverse
ANSI Very inverse
ANSI Normal Inverse
ANSI Moderately Inverse
ANSI Long Time Extremely Inverse
ANSI Long Time Very Inverse
ANSI Long Time Inverse
108
M12388-1 v21
Range or value
0.10 ≤ k ≤ 3.00
1.5 x I
≤ I ≤ 20 x I
set
set
A=28.2, B=0.1217, P=2.0 , tr=29.1
A=19.61, B=0.491, P=2.0 , tr=21.6
A=0.0086, B=0.0185, P=0.02, tr=0.46
A=0.0515, B=0.1140, P=0.02, tr=4.85
A=64.07, B=0.250, P=2.0, tr=30
A=28.55, B=0.712, P=2.0, tr=13.46
A=0.086, B=0.185, P=0.02, tr=4.6
1MRK 511 404-BEN A
Accuracy
ANSI/IEEE C37.112 ,
±2.0% or ±40 ms
whichever is greater