2 Parameters
2.2 List of parameters
p1470[0...n]
Speed controller encoderless operation P-gain / n_ctrl SL Kp
VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: REL
Min
0.000
Description:
Sets the P gain for encoderless operation for the speed controller.
Dependency:
For p0528 = 1, the speed controller gain is represented without any dimensions.
Note:
The product p0341 x p0342 is taken into account when automatically calculating the speed controller (p0340 = 1, 3,
4).
p1472[0...n]
Speed controller encoderless operation integral time / n_ctrl SL Tn
VECTOR_G (n/M)
Can be changed: U, T
Data type: FloatingPoint32
P-Group: Closed-loop control
Not for motor type: REL
Min
0.0 [ms]
Description:
Set the integral time for encoderless operation for the speed controller.
Note:
The integral component is stopped if the complete controller output or the sum of controller output and torque pre-
control reach the torque limit.
p1475[0...n]
CI: Speed controller torque setting value for motor holding brake / n_ctrl M_sv MHB
VECTOR_G (n/M)
Can be changed: T
Data type: Unsigned32 / FloatingPoint32
P-Group: Closed-loop control
Not for motor type: REL
Min
-
Description:
Sets the signal source for the torque setting value when starting up with motor holding brake.
Recommendation:
To hold the actual torque when stopping the motor, you are advised to set p1400 bit 1 = 1. As a result, the integral
component of the speed controller is frozen when changing to the open-loop controlled operating range.
Dependency:
The switching in of the torque setting value for the motor holding brake has a higher priority than the setting of the
integrator value using p1477 and p1478.
Note:
The setting of the integral output of the speed controller begins after magnetizing (see p0346, r0056 bit 4) and ends
at the end of the brake control opening time p1216. A setting value of zero means that no setting procedure will take
place.
p1476[0...n]
BI: Speed controller hold integrator / n_ctrl integ stop
VECTOR_G (n/M)
Can be changed: T
Data type: Unsigned32 / Binary
P-Group: Closed-loop control
Not for motor type: REL
Min
-
Description:
Sets the signal source to hold the integrator for the speed controller.
398
Calculated: CALC_MOD_CON
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
999999.000
Calculated: CALC_MOD_CON
Dyn. index: DDS, p0180
Unit group: -
Scaling: -
Max
100000.0 [ms]
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: p2003
Max
-
Calculated: -
Dyn. index: CDS, p0170
Unit group: -
Scaling: -
Max
-
List Manual (LH2), 07/2016, A5E03263479A
Access level: 2
Func. diagram: 6040, 6050
Unit selection: -
Expert list: 1
Factory setting
0.300
Access level: 2
Func. diagram: 6040, 6050
Unit selection: -
Expert list: 1
Factory setting
20.0 [ms]
Access level: 3
Func. diagram: 6040
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 3
Func. diagram: 2520, 5040,
5042, 5210, 6040
Unit selection: -
Expert list: 1
Factory setting
0