p0745
BI: CU signal source for terminal DI/DO 15 / CU S_src DI/DO 15
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: Unsigned32 / Binary
CU_G130_DP,
P-Group: Commands
CU_G150_DP
Not for motor type: -
Min
-
Description:
Sets the signal source for terminal DI/DO 15 (X132.13 / X131.5you).
Regarding the terminal designation:
The first designation is valid for CU320, the second for CU310.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
Prerequisite: The DI/DO must be set as an output (p0728.15 = 1).
DI/DO: Bidirectional Digital Input/Output
r0747
CU digital outputs status / CU DO status
CU_G130_PN,
Can be changed: -
CU_G150_PN,
Data type: Unsigned32
CU_G130_DP,
CU_G150_DP
P-Group: Commands
Not for motor type: -
Min
-
Description:
Displays the status of digital outputs.
Bit field:
Bit
08
09
10
11
12
13
14
15
Notice:
Regarding the terminal designation:
The first designation is valid for CU320, the second for CU310.
Note:
Inversion using p0748 has been taken into account.
DI/DO: Bidirectional Digital Input/Output
p0748
CU invert digital outputs / CU DO inv
CU_G130_PN,
Can be changed: U, T
CU_G150_PN,
Data type: Unsigned32
CU_G130_DP,
CU_G150_DP
P-Group: Commands
Not for motor type: -
Min
-
Description:
Setting to invert the signals at the digital outputs.
Bit field:
Bit
08
09
10
11
12
13
14
15
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Signal name
DI/DO 8 (X122.9/X121.7)
DI/DO 9 (X122.10/X121.8)
DI/DO 10 (X122.12/X121.10)
DI/DO 11 (X122.13/X121.11)
DI/DO 12 (X132.9/X131.1)
DI/DO 13 (X132.10/X131.2)
DI/DO 14 (X132.12/X131.4)
DI/DO 15 (X132.13/X131.5)
Signal name
DI/DO 8 (X122.9/X121.7)
DI/DO 9 (X122.10/X121.8)
DI/DO 10 (X122.12/X121.10)
DI/DO 11 (X122.13/X121.11)
DI/DO 12 (X132.9/X131.1)
DI/DO 13 (X132.10/X131.2)
DI/DO 14 (X132.12/X131.4)
DI/DO 15 (X132.13/X131.5)
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
High
High
High
High
High
High
High
High
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
-
1 signal
Inverted
Inverted
Inverted
Inverted
Inverted
Inverted
Inverted
Inverted
2 Parameters
2.2 List of parameters
Access level: 1
Func. diagram: 2119, 2133
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 1
Func. diagram: 2130, 2131,
2132, 2133
Unit selection: -
Expert list: 1
Factory setting
-
0 signal
Low
Low
Low
Low
Low
Low
Low
Low
Access level: 1
Func. diagram: 2030, 2031,
2130, 2131, 2132, 2133
Unit selection: -
Expert list: 1
Factory setting
0000 0000 0000 0000 bin
0 signal
Not inverted
Not inverted
Not inverted
Not inverted
Not inverted
Not inverted
Not inverted
Not inverted
FP
-
-
-
-
-
-
-
-