Table 5–11: FLEXLOGIC OPERANDS SUPPORTED BY AGGREGATOR
OPERAND TYPE
ELEMENT:
Synchrophasor, phasor data,
concentrator
as above
as above
as above
as above
as above
as above
as above
PMU AGGREGATOR1 PMU1 to PMU4: If set to Yes aggregator 1 will include PMU1 data set in the reporting data
stream. Aggregator 1 will not include PMU1 data set in the report if set to No. For a system frequency of 60Hz (50 Hz)
the UR will generate a Reporting Mismatch message if the selected rate isn't 10Hz, 12Hz, 15Hz, 20Hz, 30Hz, 60 Hz,
120 Hz (10Hz, 25Hz, 50Hz or 100Hz) when entered via the keypad or software and the UR will stop the transmission
of reports. Note: If changes are made to PMU settings the PMU must be removed from the aggregator and the settings
saved and then the PMU should be added back into the aggregator and the settings saved such that the new PMU set-
tings take effect.
GE Multilin
OPERAND SYNTAX
AGTR1 PDC CNTRL 1
AGTR1 PDC CNTRL 2
AGTR1 PDC CNTRL 3
AGTR1 PDC CNTRL 16
AGTR2 PDC CNTRL 1
AGTR2 PDC CNTRL 2
AGTR2 PDC CNTRL 3
AGTR1 PDC CNTRL 16
L90 Line Current Differential System
OPERAND DESCRIPTION
Phasor data concentrator asserts control bit 1, as
received via the network.
Phasor data concentrator asserts control bit 2 as
received via the network.
Phasor data concentrator asserts control bit 3 as
received via the network.
Phasor data concentrator asserts control bit 16, as
received via the network.
Phasor data concentrator asserts control bit 1 as
received via the network
Phasor data concentrator asserts control bit 2 as
received via the network
Phasor data concentrator asserts control bit 3 as
received via the network.
Phasor data concentrator asserts control bit 16, as
received via the network.