5 SETTINGS
MESSAGE
MESSAGE
MESSAGE
MESSAGE
Selected records can be cleared from user-programmable conditions with FlexLogic™ operands. Assigning user-program-
mable pushbuttons to clear specific records are typical applications for these commands. Since the L90 responds to rising
edges of the configured FlexLogic™ operands, they must be asserted for at least 50 ms to take effect.
Clearing records with user-programmable operands is not protected by the command password. However, user-program-
mable pushbuttons are protected by the command password. Thus, if they are used to clear records, the user-programma-
ble pushbuttons can provide extra security if required.
For example, to assign user-programmable pushbutton 1 to clear demand records, the following settings should be applied.
1.
Assign the clear demand function to pushbutton 1 by making the following change in the
CLEAR RELAY RECORDS
"
PUSHBUTTON 1 ON
CLEAR DEMAND:
2.
Set the properties for user-programmable pushbutton 1 by making the following changes in the
SETUP
USER-PROGRAMMABLE PUSHBUTTONS
PUSHBUTTON 1 FUNCTION:
PUSHBTN 1 DROP-OUT TIME:
GE Multilin
CLEAR DEMAND:
Off
CLEAR CHNL STATUS:
Off
CLEAR ENERGY:
Off
RESET UNAUTH ACCESS:
Off
menu:
"
USER PUSHBUTTON 1
"Self-reset"
"0.20 s"
L90 Line Current Differential System
5.2 PRODUCT SETUP
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
SETTINGS
SETTINGS
menu:
PRODUCT SETUP
PRODUCT
5
5-15