Devices specified as the device part of the OUT instruction
The following describes operations of devices specified as the device part of the OUT instruction.
Ex.
A subroutine-type FB using M0 for the device part of the OUT instruction.
SM400
EN
■ When "Yes" is selected for "Use MC/MCR in EN Control"
M0 is forcibly turned off ((1) in the following figure).
Sc
EN
M0
Sc: Scan
 EN is turned off. (User operation)
 The coil turns off. (CPU module operation)
■ When "No" is selected for "Use MC/MCR in EN Control"
The current state of M0 remains unchanged ((1) in the following figure).
Sc
EN
M0
Sc: Scan
 EN is turned off. (User operation)
 The state of coil remains unchanged. (CPU module operation)
APPX
156
Appendix 1 Operations of when the MC/MCR instructions are used to control EN
M0
ENO
END
Ò
Ó
(1)
Ò
Ó
(1)