Chapter 4 - Power Cabling
Cable Installation
1. Strip the motor and line voltage (mains) cables as outlined in the following figure
and table.
Frame
A1
B1
FS4
0.59 (15)
1.38 (35)
FS5
0.78 (20)
1.57 (40)
FS6
0.78 (20)
3.54 (90)
FS7
0.78 (20)
3.15 (80)
34 | 82
Siemens Industry, Inc.
Building Technologies
Avoid placing the motor cables in long parallel lines with other cables.
If the motor cables run in parallel with other cables note the minimum distances
between the motor cables and other cables given in the following table.
Distance Between
Shielded Cable, m
Cables, m (ft)
(ft)
1.0 (0.3)
3.2 (1.0)
≥ 656 (200)
The given distances also apply between the motor cables and signal cables of
other systems.
The maximum lengths of motor cables (shielded) are:
328 ft (100 m) (FS4)
493 ft (150 m) (FS5 and FS6)
656 ft (200 m) (FS7 to FS9).
The motor cables should cross other cables at an angle of 90 degrees.
If cable insulation checks are needed, see the
section [➙ 66].
Start the cable installation according to the instructions in the following section.

Frames FS4 to FS7

Earth conductor
C1
A1
D1
B1
MAINS
Figure 14: Stripping the Cables.
Table 15: Cable Stripping Lengths in Inches (mm).
C1
D1
C2
0.39 (10)
0.78 (20)
0.27 (7)
0.39 (10)
1.18 (30)
0.39 (10)
0.59 (15)
2.36 (60)
0.59 (15)
0.78 (20)
3.15 (80)
0.78 (20)
Siemens BT300 HVAC Drive Installation
Instructions
≤ 164 (50)
Cable and motor insulation checks
Earth conductor
C2
D2
E
MOTOR
D2
E
Leave as
1.38 (35)
short as
1.57 (40)
possible
2.36 (60)
3.15 (80)
DPD01148
2016-06-28