GE 845 Instruction Manual page 424

Transformer protection relay
Hide thumbs Also See for 845:
Table of Contents

Advertisement

FLEXLOGIC
Table 4-49: 845 FlexLogic Operands
ELEMENT
OPERANDS
Aging Factor
Aging Factor PKP
Aging Factor OP
Auxiliary OV
Aux OV PKP
Aux OV OP
Auxiliary UV
Aux UV 1 PKP
Aux UV 1 OP
Aux UV 2
Breaker Arcing
BKR1 Arc OP
BKR 2, BKR 3
Breaker Control
Local Mode ON
Local Mode OFF
BKR1 Local Open
BKR1 Local Close
BKR1 Remote Open
BKR1 Remote Close
BKR 2, BKR 3
4–320
When more complex logic than the one presented above is required, the FlexLogic™ tool
should be used. For example, if it is desired to block the operation of a Phase Time
Overcurrent element by the closed state of a contact input, and the operated state of a
Phase Undervoltage element, the two input states need be programmed in a FlexLogic™
equation. This equation ANDs the two inputs to produce a virtual output which then must
be programmed within the menu of the Phase Time Overcurrent as a blocking input.
Virtual outputs can be created only by FlexLogic™ equations.
Traditionally, protective relay logic has been relatively limited. Any unusual applications
involving interlocks, blocking, or supervisory functions had to be hard-wired using contact
inputs and outputs. FlexLogic™ minimizes the requirement for auxiliary components and
wiring while making more complex schemes possible.
The logic that determines the interaction of inputs, elements, schemes and outputs is field
programmable through the use of logic equations that are sequentially processed. The use
of virtual inputs and outputs in addition to hardware is available internally and on the
communication ports for other relays to use (distributed FlexLogic™).
FlexLogic™ allows users to customize the relay through a series of equations that consist
of operators and operands. The operands are the states of inputs, elements, schemes and
outputs. The operators are logic gates, timers and latches (with set and reset inputs). A
system of sequential operations allows any combination of specified operands to be
assigned, as inputs to specified operators, to create an output. The final output of an
equation is a numbered register called a 'Virtual Output'. Virtual Outputs can be used as an
input operand in any equation, including the equation that generates the output, as a seal-
in or other type of feedback.
A FlexLogic™ equation consists of parameters that are either operands or operators.
Operands have a logic state of 1 or 0. Operators provide a defined function, such as an
AND gate or a Timer. Each equation defines the combinations of parameters to be used to
set a Virtual Output flag. Evaluation of an equation results in either a 1 (=ON, i.e. flag set) or
0 (=OFF, i.e. flag not set). Each equation is evaluated at least 4 times during every power
system cycle.
Some types of operands are present in the relay in multiple instances; e.g. contact and
remote inputs. These types of operands are grouped together (for presentation purposes
only) on the faceplate display. The characteristics of the different types of operands are
listed in the table below.
EVENT DESCRIPTION
The Aging factor element has picked up
The Aging factor element has operated
Auxiliary overvoltage element has picked up
Auxiliary overvoltage element has operated
Auxiliary undervoltage element 1 has picked up
Auxiliary undervoltage element 1 has operated
The same set of operands as per Aux UV 1
Breaking arcing 1 element operated
Same set of operands as for BKR 1
Local Mode for breaker control is turned on
Local Mode for breaker control is turned off
Breaker Open command is initiated from the PB "Open"
Breaker 1 Close command is initiated from the PB "Close"
Breaker Open command is initiated from the conf. input
Breaker 1 Close command is initiated from the conf. input
Same set of operands as fro BKR 1
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 4: SETPOINTS

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents