Inputs; Power Supply - GE T35 Instruction Manual

Transformer management relay
Hide thumbs Also See for T35:
Table of Contents

Advertisement

2.2 SPECIFICATIONS
AC CURRENT
CT rated primary:
CT rated secondary:
Nominal frequency:
Relay burden:
2
Conversion range:
Standard CT:
Sensitive Ground module:
0.002 to 4.6 × CT rating RMS symmetrical
Current withstand:
AC VOLTAGE
VT rated secondary:
VT ratio:
Nominal frequency:
Relay burden:
Conversion range:
Voltage withstand:
CONTACT INPUTS
Dry contacts:
Wet contacts:
Selectable thresholds:
Tolerance:
Recognition time:
Debounce timer:
DCMA INPUTS
Current input (mA DC): 0 to –1, 0 to +1, –1 to +1, 0 to 5, 0 to 10,
Input impedance:
Conversion range:
Accuracy:
Type:
LOW RANGE
Nominal DC voltage:
Min/max DC voltage:
NOTE: Low range is DC only.
HIGH RANGE
Nominal DC voltage:
Min/max DC voltage:
Nominal AC voltage:
Min/max AC voltage:
2-8
1 to 50000 A
1 A or 5 A by connection
20 to 65 Hz
< 0.2 VA at rated secondary
0.02 to 46 × CT rating RMS symmetrical
20 ms at 250 times rated
1 sec. at 100 times rated
continuous at 3 times rated
50.0 to 240.0 V
1.00 to 24000.00
20 to 65 Hz
< 0.25 VA at 120 V
1 to 275 V
continuous at 260 V to neutral
1 min./hr at 420 V to neutral
1000 Ω maximum
300 V DC maximum
17 V, 33 V, 84 V, 166 V
±10%
< 1 ms
0.0 to 16.0 ms in steps of 0.5
0 to 20, 4 to 20 (programmable)
379 Ω ±10%
–1 to + 20 mA DC
±0.2% of full scale
Passive
24 to 48 V at 3 A
20 / 60 V
125 to 250 V at 0.7 A
88 / 300 V
100 to 240 V at 50/60 Hz, 0.7 A
88 / 265 V at 48 to 62 Hz
T35 Transformer Management Relay
2 PRODUCT DESCRIPTION
RTD INPUTS
100 Ω Platinum, 100 & 120 Ω Nickel, 10
Types (3-wire):
Ω Copper
Sensing current:
5 mA
Range:
–50 to +250°C
Accuracy:
±2°C
Isolation:
36 V pk-pk
IRIG-B INPUT
Amplitude modulation:
1 to 10 V pk-pk
DC shift:
TTL
Input impedance:
22 kΩ
Isolation:
2 kV
REMOTE INPUTS (MMS GOOSE)
Number of input points: 32, configured from 64 incoming bit pairs
Number of remote devices:16
Default states on loss of comms.: On, Off, Latest/Off, Latest/On
DIRECT INPUTS
Number of input points: 32
No. of remote devices:
16
Default states on loss of comms.: On, Off, Latest/Off, Latest/On
Ring configuration:
Yes, No
Data rate:
64 or 128 kbps
CRC:
32-bit
CRC alarm:
Responding to:
Rate of messages failing the CRC
Monitoring message count: 10 to 10000 in steps of 1
Alarm threshold:
1 to 1000 in steps of 1
Unreturned message alarm:
Responding to:
Rate of unreturned messages in the ring
configuration
Monitoring message count: 10 to 10000 in steps of 1
Alarm threshold:
1 to 1000 in steps of 1
ALL RANGES
2 × Highest Nominal Voltage for 10 ms
Volt withstand:
Voltage loss hold-up:
50 ms duration at nominal
Power consumption:
Typical = 15 VA; Max. = 30 VA
INTERNAL FUSE
RATINGS
Low range power supply: 7.5 A / 600 V
High range power supply: 5 A / 600 V
INTERRUPTING CAPACITY
AC:
100 000 A RMS symmetrical
DC:
10 000 A

2.2.5 INPUTS

2.2.6 POWER SUPPLY

GE Multilin