Mitsubishi Electric CAHV-P500YA-HPB Instruction Manual page 19

Air-cooled heat pump unit cahv series
Hide thumbs Also See for CAHV-P500YA-HPB:
Table of Contents

Advertisement

*1 Under normal heating conditions at the outdoor temperature of 7ºCDB/6ºCWB (44.6ºFDB/42.8ºFWB)
and the outlet water temperature of 45ºC (113ºF)
*2 Under normal heating conditions at the outdoor temperature of 7ºCDB/6ºCWB (44.6ºFDB/42.8ºFWB)
and outlet water temperature of 70ºC (158ºF)
*3 Under normal heating conditions at the outdoor temperature of 7ºCDB/6ºCWB (44.6ºFDB/42.8ºFWB)
and the unit is set to the "Capacity Priority" mode through the no-voltage A-contact.
*4
・Due to continuing improvements, specifications may be subject to change without notice.
・Do not use steel pipes as water pipes.
・Keep the water circulated at all times. Blow the water out of the pipes if the unit will not be used for an
extended period of time.
・Do not use ground water or well water.
・Do not install the unit in an environment where the wet bulb temperature exceeds 32ºC.
・The water circuit must be a closed circuit.
Unit converter
Kcal = kW x 860
BTU/h = kW x 3.412
3
cfm = m
/min x 35.31
Lb = kg/0.4536
19/20