Error
code *1
(PCB *2)
Heat exchanger freeze up
1104
Inverter
Electric
IPM error
error
current
4250
related
4255
errors
101
(
)
during
opera-
tion
4250
ACCT overcurrent
4255
102
(
)
4250
DCCT overcurrent
4255
103
(
)
4250
Overcurrent relay trip (effective value)
4255
(During operation)
107
(
)
4250
Overcurrent relay trip (momentary value)
4255
(During operation)
106
(
)
4250
Short-circuited IPM/ground fault
4255
(During operation)
104
(
)
4250
Overcurrent error due to a short-circuited
4255
(During operation)
105
(
)
Current-
IPM error
related
(At startup)
4250
pro-
4255
blems
101
(
)
at start
up
4250
ACCT overcurrent
4255
(At startup)
102
(
)
4250
DCCT overcurrent
4255
(At startup)
103
(
)
4250
Overcurrent relay trip (effective value)
4255
(At startup)
107
(
)
4250
Overcurrent relay trip (momentary value)
4255
(At startup)
106
(
)
Voltage-
Bus voltage drop protection
4220
related
4225
pro-
108
(
)
blems
during
4220
Bus voltage rise protection
opera-
4225
tion
109
(
)
Logic error
4220
4225
111
(
)
4220
Voltage meter error at start up
4225
(Bus voltage drop protection at start up (detected
131
(
)
by the Main unit side))
Heatsink fault
(Heatsink overheat protection)
4230
4235
Overload protection
4240
4245
5301
ACCT sensor fault
5305
115
(
)
Error type
*6 Drop in water flow or water supply cutoff
Cause
(Installation/Setting error)
during the defrost cycle
Water temperature drop during defrost cycle
Inter-phase voltage drop
(Inter-phase voltage at or below 180 V)
Momentary power failure/power failure
Power supply voltage drop (Inter-phase
voltage is 180 V or below.)
Voltage drop
Incorrect power supply voltage
Malfunction due to external noise interference
•
Faulty grounding
•
Improper transmission and external
wiring installation
(Shielded cable is not used.)
•
Low-voltage signal wire and high-voltage
wire are in contact.
(Placing the signal wire and power wire
in the same conduit)
Power supply voltage drop
Power supply voltage drop (Inter-phase
voltage is 180 V or below.)
Clogged heatsink cooling air passage
Short-cycling of air (reduced air flow)
Clogged heatsink cooling air passage
Power supply voltage drop (Inter-phase
voltage is 180 V or below.)
10/20
Cause
(Parts problems)
•
4-way valve switching failure
•
INV board fault
•
Ground fault of the compressor
•
Coil problem
•
IPM error (loose terminal screws,
cracked due to swelling)
•
Items listed under "Heatsink overheat
protection" below
•
INV board fault
•
Ground fault of the compressor
•
Coil problem
•
IPM error (loose terminal screws,
cracked due to swelling)
•
Ground fault of the compressor
•
IPM error (loose terminal screws,
cracked due to swelling)
•
Ground fault of the compressor
•
Shorted output wiring
•
INV board fault
•
Ground fault of the compressor
•
Coil problem
•
IPM error (loose terminal screws,
cracked due to swelling)
•
Items listed under "Heatsink overheat
protection" below
•
INV board fault
•
Ground fault of the compressor
•
Coil problem
•
IPM error (loose terminal screws,
cracked due to swelling)
•
INV board CNDC2 wiring fault
•
INV board fault
•
72C fault
•
Diode stack failure
•
INV board fault
•
INV board fault
•
PCB fault
•
Fan motor fault
•
INV board fan output fault
•
THHS sensor fault
•
IPM error (loose terminal screws,
cracked due to swelling)
•
THHS sensor fault
•
Current sensor fault
•
INV board fan output fault
•
INV circuit fault
•
Compressor fault
•
INV board fault
•
Ground fault of the compressor and
IPM error
Error reset *3
Unit
side
Remote
(PCB)
Operation